Performance Under Rated Conditions * - Models STR94G (0 to 500 psi/35 bar)
Parameter
Description
Upper Range Limit
psi
bar
500
35
Minimum Span
psi
bar
20
1.4
Turndown Ratio
25 to 1
Zero Elevation and Suppression No limit except minimum span from absolute 0 (zero) to +100% URL.
Accuracy
(Reference – Includes
combined effects of linearity,
hysteresis, and repeatability)
• Accuracy includes residual error
after averaging successive
readings.
• For F
OUNDATION
Fieldbus use
Digital Mode specifications. For
HART use Analog Mode
specifications.
In Analog Mode:
±0.10% of calibrated span or upper range value (URV), whichever is
greater, terminal based.
In Digital Mode:
±0.075% of calibrated span or upper range value (URV), whichever
is greater, terminal based.
* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
Transmitter Minimum Span and Maximum Capillary Length
Minimum recommended span for STR93D DP Transmitter with two Remote Seals
Diaphragm
Capillary Length
Size
5'
10'
15'
20'
25'
30'
35'
maximum
2.0
15 psig
20 psig
25 psig
-
-
-
-
15'
2.4
150 iwc
200 iwc
250 iwc
300 iwc
350 iwc
400 iwc
450 iwc
35'
2.9
50 iwc
75 iwc
100 iwc
125 iwc
150 iwc
175 iwc
200 iwc
35'
3.5
25 iwc
25 iwc
25 iwc
28 iwc
32 iwc
36 iwc
40 iwc
35'
4.1
25 iwc
25 iwc
25 iwc
25 iwc
25 iwc
27 iwc
30 iwc
35'
Minimum recommended span for STR94G or STR93D DP Transmitter with one Remote Seal
Diaphragm
Direct
Capillary Length
Size
Mount
5'
10'
15'
20'
30'
35'
maximum
2.0
25 psi
30 psi
40 psi
50 psi
-
-
-
15'
2.4
10 psi
15 psi
20 psi
25 psi
30 psi
40 psi
50 psi
35'
2.9
8 psi
9 psi
10 psi
11 psi
12 psi
14 psi
15 psi
35'
3.5
2 psi
2 psi
3 psi
4 psi
5 psi
7 psi
8 psi
35'
4.1
0.9 psi
0.9 psi
1 psi
2 psi
3 psi
4 psi
5 psi
35'
Minimum span is the higher of the value from the table above or the value defined under Performance Conditions for the range transmitter
Capillary
Capillary
Figure 15—
Maximum capillary length and diaphragm size chart.
Performance Under Rated Conditions - General for all Models
Parameter
Description
Output (two-wire)
Analog 4 to 20 mA or DE digital communications mode. Options available for
F
OUNDATION
Fieldbus and HART protocols.
Supply Voltage Effect
0.005% of span per volt.
Damping Time Constant
Adjustable from 0 to 32 seconds digital damping.
CE Conformity (Europe)
89/336/EEC, Electromagnetic Compatibility (EMC) Directive.
NAMUR NE 43 Compliance
Option
Transmitter failure information is generated when the measuring information is invalid or
no longer present. Failure information is transmitted as a current signal but outside the
normal 4-20 mA measurement signal level. Transmitter failure values are:
≤ 3.6 mA and ≥ 21.0 mA. The normal signal range is ≥ 3.8 mA and ≤ 20.5 mA.
SIL 2/3 Compliance
SIL certified to IEC 61508 for non-redundant use in SIL 2 related Safety Systems
(single use) and for redundant (multiple) use in SIL 3 Safety Systems through
TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 1998;
IEC 61508-2: 2000; IEC61508-3: 1998.