beautypg.com

Sil 2/3 compliance, Parameter description, Figure 15 – Honeywell ST 3000 SMART TRANSMITTER STR93D User Manual

Page 8: Maximum capillary length and diaphragm size chart

background image

34-ST-03-57
Page 8

Performance Under Rated Conditions * - Models STR94G (0 to 500 psi/35 bar)

Parameter

Description

Upper Range Limit

psi

bar

500
35

Minimum Span

psi

bar

20
1.4

Turndown Ratio

25 to 1

Zero Elevation and Suppression No limit except minimum span from absolute 0 (zero) to +100% URL.

Accuracy

(Reference – Includes

combined effects of linearity,
hysteresis, and repeatability)

Accuracy includes residual error

after averaging successive
readings.

For F

OUNDATION

Fieldbus use

Digital Mode specifications. For
HART use Analog Mode
specifications.

In Analog Mode:

±0.10% of calibrated span or upper range value (URV), whichever is

greater, terminal based.

In Digital Mode:

±0.075% of calibrated span or upper range value (URV), whichever

is greater, terminal based.

* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.

Transmitter Minimum Span and Maximum Capillary Length

Minimum recommended span for STR93D DP Transmitter with two Remote Seals

Diaphragm

Capillary Length

Size

5'

10'

15'

20'

25'

30'

35'

maximum

2.0

15 psig

20 psig

25 psig

-

-

-

-

15'

2.4

150 iwc

200 iwc

250 iwc

300 iwc

350 iwc

400 iwc

450 iwc

35'

2.9

50 iwc

75 iwc

100 iwc

125 iwc

150 iwc

175 iwc

200 iwc

35'

3.5

25 iwc

25 iwc

25 iwc

28 iwc

32 iwc

36 iwc

40 iwc

35'

4.1

25 iwc

25 iwc

25 iwc

25 iwc

25 iwc

27 iwc

30 iwc

35'

Minimum recommended span for STR94G or STR93D DP Transmitter with one Remote Seal

Diaphragm

Direct

Capillary Length

Size

Mount

5'

10'

15'

20'

30'

35'

maximum

2.0

25 psi

30 psi

40 psi

50 psi

-

-

-

15'

2.4

10 psi

15 psi

20 psi

25 psi

30 psi

40 psi

50 psi

35'

2.9

8 psi

9 psi

10 psi

11 psi

12 psi

14 psi

15 psi

35'

3.5

2 psi

2 psi

3 psi

4 psi

5 psi

7 psi

8 psi

35'

4.1

0.9 psi

0.9 psi

1 psi

2 psi

3 psi

4 psi

5 psi

35'

Minimum span is the higher of the value from the table above or the value defined under Performance Conditions for the range transmitter

Capillary

Capillary

Figure 15

Maximum capillary length and diaphragm size chart.


Performance Under Rated Conditions - General for all Models

Parameter

Description

Output (two-wire)

Analog 4 to 20 mA or DE digital communications mode. Options available for
F

OUNDATION

Fieldbus and HART protocols.

Supply Voltage Effect

0.005% of span per volt.

Damping Time Constant

Adjustable from 0 to 32 seconds digital damping.

CE Conformity (Europe)

89/336/EEC, Electromagnetic Compatibility (EMC) Directive.

NAMUR NE 43 Compliance
Option

Transmitter failure information is generated when the measuring information is invalid or
no longer present. Failure information is transmitted as a current signal but outside the
normal 4-20 mA measurement signal level. Transmitter failure values are:
≤ 3.6 mA and ≥ 21.0 mA. The normal signal range is ≥ 3.8 mA and ≤ 20.5 mA.

SIL 2/3 Compliance

SIL certified to IEC 61508 for non-redundant use in SIL 2 related Safety Systems

(single use) and for redundant (multiple) use in SIL 3 Safety Systems through

TÜV Nord Sys Tec GmbH & Co. KG under the following standards: IEC61508-1: 1998;

IEC 61508-2: 2000; IEC61508-3: 1998.

This manual is related to the following products: