beautypg.com

Honeywell UMC800 User Manual

Page 14

background image

Equipment Identification
Controller Components

6

UMC800 Controller Installation and User Guide

Release F

4/01

I/O modules

Eleven different module types can be installed in the controller to support both analog and digital inputs
and outputs of various types and signal levels. The signal type and I/O capacity for each module type is
indicated in Table 1.

Table 1 Controller plug-in I/O module types

Module Type

Signal Types

Maximum

I/O

I/O per

card

Maximum no.

of cards

Universal Analog Inputs (AI)

mV, V, mA, T/C, RTD, Ohms

64

4

16

Analog Outputs (AO)

0 mA to 20 mA

16

4

4

Digital Inputs (DI) - 4 types:

AC

100/240 Vac

96

6

16

DC

24 Vdc

96

6

16

Logic

Dry contacts
(5 mA - 5 Vdc)

96

6

16

16 point

Dry contacts

48

16

3

Digital Outputs (DO) - 4 types:

AC

100/240 Vac

96

6

16

AC
High current outputs

100/240 Vac
With:
2 outputs rated @ 2 A
4 outputs rated @ 0.5 A

12

2

12

DC

24 Vdc

96

6

16

Relay

SPST normally open (NO) or
normally closed (NC) contact.
(User configurable)

60

6

10

Pulse Input/Frequency Input

24 Vdc

64

4

16

pH Power Module

± 15 Vdc

8

4

2

NOTE: Total combined digital I/O is 96 points.

Control architecture

The UMC800 uses a function block configuration architecture to develop control strategies for both analog
and digital operations. A function block may represent a physical input or output, a group of physical inputs
or outputs, an internal calculation, or an internal function such as a PID algorithm. More than 70 standard
UMC800 function block algorithm types are available for configuring analog and logic functions.
Typically, a function block algorithm type may be used any number of times up to the limit of 250 blocks.
Some of these with specific limitations are:

Control loops (i.e., PID, ON/OFF, TPSC, and Carbon potential)—eight or sixteen maximum

Setpoint programmer and associated support blocks—four maximum

Setpoint Scheduler and associated support blocks—one maximum

Time proportioning output blocks—sixteen maximum

Pushbutton blocks—four maximum

4 Selector Switch blocks—four maximum

Modbus Slave blocks—sixteen maximum