EXCEL 10 W7761A INPUT/OUTPUT DEVICE
48
74-2699
Table C1. Input/Output Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Calibrate (C), Monitor (M),
Parameter (P), Schematic (S)
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH
MA
DA
EV
HW
MN
TS
Comments
X
X
X
M
DestOut1Cmd: DestOut1Cmd through DestOut8Cmd corresponds to DO1 through
DO8. Refer to the Eng. Units/States column for DO1Type for the enumerated
values that can be assigned to any output channels.
Note that a selection of FLOAT means that the two DO channels are used for
output. RIO assumes that the tool makes the proper assignment of enumerated
values to DO1 through DO8 and also takes the responsibility to avoid assignment
of multiple or overlapping commands on the same output channels. An example of
the relationship between nviRemoteCmd and ncirioIoSelect is discribed below:
RIO is receiving a command to DestOut4Cmd. This can be mapped as one of the
three output types (Discrete, Modulate, Float_Open, or Float_Close) by DO3Type.
If the user selects an enumerated value of Discrete2 for DO3Type, this value would
be stored in (DO2). Then the DestOut4Cmd will command DO2.
X
X
X
M
DestOut2Cmd: Refer to the description for DestOut1Cmd.
X
X
X
M
DestOut3Cmd: Refer to the description for DestOut1Cmd.
X
X
X
M
DestOut4Cmd: Refer to the description for DestOut1Cmd.
X
X
X
M
DestOut5Cmd: Refer to the description for DestOut1Cmd.
X
X
X
M
DestOut6Cmd: Refer to the description for DestOut1Cmd.
X
X
X
M
DestOut7Cmd: Refer to the description for DestOut1Cmd.
X
X
X
M
DestOut8Cmd: Refer to the description for DestOut1Cmd.
X
X
DI1Sel1Type specifies the sensor type and function connected to DigitalIn0S1
through DigitalIn3S1. The valid enumerated list of logical digital states for
DigitalIn0S1 is listed in the Eng. Units/States column.
X
X
DI2Sel1Type: Refer to the description for DI1Sel1Type.
(continued)