34-ST-99-25 (Addendum to 33-ST-33-39)

10/04

Additions to the
Installation Guide

The additions to Installation Guide 34-ST-33-39 that relate to the newly designed meter
body and process heads are given in Table 1 of this addendum. Use the information in
Table 1 to reference and annotate your User Manual.

Table 1 – Additions to the User Manual

Page # in User

Manual

Sub-Section Description

of

Change

19

3.3 Considerations for ST 3000
Transmitter

Table 6 Transmitter
Overpressure Ratings

The Maximum Working Pressure Rating and the
Overpressure Rating has been enhanced for all
models included in this addendum except for the
draft range transmitter.

For more information, refer to Table 3 in this
Addendum.

38

4.2 Piping ST3000 Transmitter

Table 15 Installing Flange
Adapter

In Step 2 and in Step 4, the reference to the “Teflon
(white) gasket should be “gasket or O-ring”.

In Step 5, do not use the torque specification of 47.5
to 54 N·m (35 to 40 ft-lb). Instead, use the
following:
47,5 N

m +/- 2,4 Nm (35 Lb-Ft +/- 1.8 Lb-Ft).

46

5.1 Wiring Diagrams and
Dimension Drawings

Dimension drawings-Series 100
and Series 900

The numbers of dimension drawings for the newly
designed models are given in Table 2 in this
addendum.