Henny Penny BCM-110 User Manual
Page 7
Model BCF-24/65/110, BCM-110
1-3. TROUBLESHOOTING
(Continued)
Problem
Cause
Correction
Slow to decrease
Condenser obstructed by dirt
Clean the condenser
in temperature (decline in
performance)
Evaporator iced up
Perform a De-icing Cycle
Refrigerating problem
Check refrigeration circuit and
components
Display temperature does
In Frigiprobe Mode, the display
Normal
not match the actual inlet air
shows the product temperature
temperature (No alarm)
In timer mode, or hold mode,
Ohm out the probe and check
the probe may be showing the
the reading with the table located
wrong temperature
in this section; change the probe
if it is out of tolerance
Green compressor indicator
Compressor and condenser fan
light on and the compressor
do not work:
not working, or working
- Faulty contactor
Check contactor and change if
sometimes
necessary
- Faulty control board relay-no
Replace control board
voltage across terminals 10-11
Compressor works, but condenser
fan does not:
- Faulty condenser fan
Replace fan
Compressor and condenser fan
work together:
- Faulty protection component
Check items and replace if
for the compressor (overload
necessary
protector, potential relay, start
and run capacitor)
- Faulty overload protector of
Check fan and replace if
condenser fan
necessary