Altronix StrikeIt1 Panic Device Power Controller User Manual
Strikeit1 panic device power controller

StrikeIt1
Panic Device Power Controller
Rev. DSStrikeIt1_08182014
StrikeIt1 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is
designed to handle the high current surge panic hardware locking devices demand. Each
lock output has an adjustable relock delay timer. It will control a pair of doors simulta-
neously or independently control two individual doors. It has a follower relay for each
output to trigger external relays, ADA push plate switches, etc. Delayed follower relays
control automatic door operators for doors that are always locked or for doors that are
unlocked during the business day. In addition, two un-switched auxiliary voltage outputs
are provided for powering card readers, keypads, REX PIRs, electronic timers, relays,
etc. A configurable FACP interface will either provide power or remove power to the
lock outputs when activated. LED status indicators are provided to monitor AC power,
FACP status and for lock output wiring supervision. Intelligent logic provides protection
against accidental shorting of lock outputs.
Overview
Specifications
StrikeIt1
(order batteries separately)
Input:
• Input 115VAC 60Hz, 6.3 amp.
• Two (2) NO trigger inputs.
• Input fuse rating: 6.3 amp.
Outputs:
• Power options:
- Two (2) 20VDC to 26.4VDC individually
controlled lock outputs for applications with
battery back-up. 24VDC for applications without
battery back-up (US applications only).
Current rating 15 amp for 300ms, 0.75 amp
continuous supply current.
- 5V holding voltage with 20VDC to 26.4VDC
initial 100ms pulse. Maximum total 5V holding
current of both outputs is 0.74 amp.
• One (1) 20VDC to 26.4VDC for applications with
battery back-up, 24VDC for applications in US not
requiring battery back-up. Auxiliary output rated
@ 0.75 amp continuous supply current
(Not affected by FACP trigger).
• One (1) 12VDC filtered regulated auxiliary output
rated @ 0.75 amp in alarm, 0.5 amp stand-by current
(Not affected by FACP trigger).
• Two (2) follower form “A” SPST relay outputs rated
@ 0.6 amp/28VDC. Relays energize while
input is closed.
• Two (2) delayed follower Normally Open relay
outputs rated @ 0.6 amp/28VDC. Delay time is
selectable 0.5 seconds or 1 second.
Energized duration is 1 second.
• Trouble relay output indicating low DC output voltage.
Battery Backup:
• Battery leads included.
• Battery fuse rating: 25A/32V.
• Maximum charge current 650mA.
• Built-in charger for sealed lead acid or gel
type batteries.
• Automatic switch over to stand-by battery when AC fails.
• When 7AH batteries are used, battery capacity
for emergency stand-by is 30 minutes.
Visual Indicators:
• Green AC Power LED indicates 115VAC present.
• Red trigger input LEDs indicate panic device
status/trouble (activated, short or open circuit).
• Green Fire Alarm Interface (FAI) LED indicates
FACP disconnect is activated.
• Red Battery LED indicates low battery during
AC failure and manual test.
• Green AC LED indicates loss of AC trouble
(not active during manual test sequence).
Fire Alarm Disconnect:
• Normally Closed FACP trigger input.
• Programmable Fire Alarm Disconnect options:
- Removes power to outputs and disables delayed
follower relays.
- Connects power to lock outputs and enables
delayed follower relays.
Additional Features:
• Manual testing to allow to tests battery conditions.
• Adjustable panic release from 1 sec. to 30 secs.
Note: Follower and Delay relay turns off when the
potentiometer selected time elapses after release
of the input trigger.
• Cam lock included.
Electrical:
• Operating temperature: 0º C to 49º C ambient.
• BTU/Hr.: 196.5 BTU/Hr.
• System AC input VA requirement: 218.5VA.
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25”
(342.9mm x 330.2mm x 82.55mm)
• Enclosure accommodates up to two (2)
12VDC/7AH batteries.
• Product weight (approx.): 6.25 lbs. (2.83 kg).
• Shipping weight (approx.): 7.15 lbs. (3.24 kg).