32 40033 UINT32 pulse count 17 MSW
33 40034 UINT32 pulse count 17 LSW
34 40035 UINT32 pulse count 18 MSW
35 40036 UINT32 pulse count 18 LSW
36 40037 UINT32 pulse count 19 MSW
37 40038 UINT32 pulse count 19 LSW
38 40039 UINT32 pulse count 20 MSW
39 40040 UINT32 pulse count 20 LSW
40 40041 UINT32 pulse count 21 MSW
41 40042 UINT32 pulse count 21 LSW
42 40043 UINT32 pulse count 22 MSW
43 40044 UINT32 pulse count 22 LSW
44 40045 UINT32 pulse count 23 MSW
45 40046 UINT32 pulse count 23 LSW
System information points:
------- ------- ------- ------------------
offset point type description
1000 41001 UINT16 Serial Number (bytes 1,2) (our serial number)
1001 41002 UINT16 Serial Number (bytes 3,4)
1002 41003 UINT16 Serial Number (bytes 5,6)
1003 41004 UINT16 firmware version major
1004 41005 UINT16 firmware version minor
1005 41006 UINT32 mfg date MSW
1006 41007 UINT32 mfg date LSW
1007 41008 UINT32 up time (seconds) MSW.
1008 41009 UINT32 up time (seconds) LSW.
1009 41010 UINT16 Our modbus address
1010 41011 UINT16 Hardware Version major (8911)
1011 41012 UINT16 Hardware Version minor. HighByte=pcb-rev(0=rev A, etc),
lowbyte = part-rev (0=rev A, etc)
1012 41013 UINT16 (NV/r/w) contact closure threshold in ohms, default 1000 =
1kohm. 100-2550 ohms allowed.
1013 41014 UINT16 (NV/r/w) contact closure speed, pulse speed:
0=10hz/default, 1=50hz, 2=100hz
1014 41015 UINT16 (NV/r/w) Pulse KYZ flag bitmap. channels 1-16 0x01 =
pulse1 kyz mode, 0x02 = p2, etc.
1015 41016 UINT16 (NV/r/w) Pulse KYZ flag bitmap. channels 17-23
1016 41017 UINT16 power supply voltage monitor. scale: x100
1017 41018 UINT16 pcb temperature monitor. scale: x100
1018 41019 UINT16 5V internal power supply voltage monitor. scale: x100
1019 41020 UINT16 RS485 baud rate. 2=9600, 3=19200.
1020 41021 UINT16 reason for reboot. 0x01=POR, 0x02=EXTR 0x04=WDTR
0x08=BODR, 0x8000=WDTOF
Modbus function 0x11 Slave ID response will report the following:
"Obvius, A8911-23, pulse counter, 23 channel", id=47