beautypg.com

Water connections, Page 10 – Dunkirk Hotline Indirect Water Heater User Manual

Page 10

background image

Page 10

BOILER

SYSTEM
SUPPLY

CIRCULATOR

PUMP

BOILER

SYSTEM
RETURN

BOILER

COLD

1"

INLET

WATER HEATER

INDIRECT

HOT OUT

DOMESTIC

1 1/2"

BOILER

FROM

TO

BOILER

CHECK

VALVE

BOILER

SUPPLY

SYSTEM

DOMESTIC

3/4"

HOT OUT

INDIRECT

WATER HEATER

BOILER

TO

BOILER

FROM

COLD
INLET

3/4"

VALVE

CHECK

PUMP

CIRCULATOR

RETURN

SYSTEM

BOILER

BOILER

1" NPT

1" NPT

1" NPT

1" NPT

BOILER

SYSTEM
SUPPLY

CIRCULATOR

PUMP

BOILER

SYSTEM
RETURN

BOILER

COLD

1"

INLET

WATER HEATER

INDIRECT

HOT OUT

DOMESTIC

1 1/2"

BOILER

FROM

TO

BOILER

CHECK

VALVE

BOILER

SUPPLY

SYSTEM

DOMESTIC

3/4"

HOT OUT

INDIRECT

WATER HEATER

BOILER

TO

BOILER

FROM

COLD
INLET

3/4"

VALVE

CHECK

PUMP

CIRCULATOR

RETURN

SYSTEM

BOILER

BOILER

1" NPT

1" NPT

1" NPT

1" NPT

Figure 7: HL80SK, HL119SK water connections

SECTION IV: INSTALLATION

WATER CONNECTIONS

All piping between the boiler and the indirect heater should be new copper with a
minimum size of 3/4” ID for models HL30SK, HL40SK, and HL50SK. Use 1” minimum copper
for models HL80SK and HL119SK. Elbows should be minimized. A flow check valve must be
installed on the return line.

All piping to the inlet (cold) and outlet (hot) domestic water connections should be new
copper with a minimum size of 1/2” ID for models HL30SK, HL40SK, and HL50SK. Use 3/4”
ID minimum for models HL80SK and HL119SK.

All piping should conform to local codes and ordinances. At a minimum, refer to IHLR 84
code if local codes are not in place. It is recommended that all piping be adequately
insulated with approved material to ensure minimum heat loss. If a re-circulation line is
used for domestic water, be certain that all lines are well insulated and the circulator is
temperature controlled. Install isolation valves to permit proper servicing. It is also
recommended to install a union on the domestic outlet to facilitate replacement of the hot
outlet / anode nipple on models HL30SK, HL40SK, and HL50SK.

See Figures 6 and 7 for proper water connection installation.

HL

Note: Indirect may be connected to a steam
boiler provided that all piping to and from
the boiler are below the water line of the boiler.
Boiler must also be protected by a low water
cut off safety device.

Figure 6: HL30SK, HL40SK, HL50SK

water connections