5 - VENTILATION & COMBUSTION AIR

Provide combustion air and ventilation air in accordance

with the section “Air for Combustion and Ventilation,” of

the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or

applicable provisions of local building codes.

Provide make-up air where exhaust fans, clothes dryers,

and kitchen ventilation equipment interfere with proper

operation.

National Fuel Gas Code recognizes several methods

of obtaining adequate ventilation and combustion air.

Requirements of the authority having jurisdiction may

override these methods.

• Engineered Installations. Must be approved by

authority having jurisdictions.

• Mechanical Air Supply. Provide minimum of 0.35

cfm per Mbh for all appliances located within space.

Additional requirements where exhaust fans installed.

Interlock each appliance to mechanical air supply

system to prevent main burner operation when

mechanical air supply system not operating.

• All Indoor Air. Calculate minimum volume for all

appliances in space. Use a different method if

minimum volume not available.

о Standard Method. Cannot be used if known air

infi ltration rate is less than 0.40 air changes per

hour. See Table 3 for space with boiler only. Use

equation for multiple appliances.
Volume ≥ 50 ft

3

x Total Input [Mbh]

о Known Air Infi ltration Rate. See Table 3 for

space with boiler only. Use equation for multiple

appliances. Do not use an air infi ltration rate

(ACH) greater than 0.60.
Volume ≥ 21 ft

3

/ACH x Total Input [Mbh]

о Refer to National Fuel Gas Code for opening

requirements between connection indoor spaces.

• All Outdoor Air. Provide permanent opening(s)

communicating directly or by ducts with outdoors.

о Two Permanent Opening Method. Provide opening

commencing within 12 inches of top and second

opening commencing within 12 inches of bottom

enclosure.

 Direct communication with outdoors or

communicating through vertical ducts. Provide

minimum free area of 1 in

2

per 4 Mbh of total

input rating of all appliances in enclosure.

 Communicating through horizontal ducts.

Provide minimum free area of 1 in

2

per 2

Mbh of total input rating of all appliances in

enclosure.

о One Permanent Opening Method. Provide opening

commencing within 12 inches of top of enclosure.

Provide minimum clearance of 1 inch on sides

and back and 6 inches on front of boiler (does not

supersede clearance to combustible materials).

о Combination Indoor and Outdoor Air. Refer to

National Fuel Gas Code for additional requirements

for louvers, grilles, screens and air ducts.

• Combination Indoor and Outdoor Air. Refer to

National Fuel Gas Code for application information.

National Gas and Propane Installation Code Requires

providing air supply in accordance with:

• Section 8.2 and 8.3 when combination of appliances

has a total input of up to and including 400 Mbh (120

kW).

• Section 8.4 when combination of appliances has total

input exceeding 400 Mbh (120 kW).

• Refer to Natural Gas and Propane Installation Code

for specifi c air supply requirements for enclosure

or structure where boiler is installed, including air

supply openings and ducts.

Table 3 - Ventilation & Combustion Air

Input Mbh

Standard

Method

Known Air Infi ltration Rate Method ACH (Air Changes Per Hour)

0.1

0.2

0.3

0.4

0.5

0.6

50

2500

10500

5250

3500

2625

2100

1750

75

3750

15750

7875

5250

3938

3150

2625

100

5000

21000

10500

7000

5250

4200

3500

125

6250

26250

13125

8750

6563

5250

4375

150

7500

31500

15750

10500

7875

6300

5250

170

8500

35700

17850

11900

8925

7140

5950

200

10000

42000

21000

14000

10500

8400

7000