Propane gas, Table 1 – first stage pipe sizing, Page 8 – Louisville Tin and Stove BFT101 User Manual
Page 8
TABLE 1 – first stage pipe sizing
10 PSIG Inlet with a 1 PSIG Pressure Drop
Maximum capacity of pipe or tubing, in thousands of BTU/hr. of L.P. Gas
Size of Pipe
LENGTH OF PIPE OR TUBING, FEET*
Or Copper
Tubing, Inches
1 0
2 0
3 0
4 0
5 0
6 0
7 0
8 0
9 0
1 0 0
3/8
5 58
3 83
30 9
265
2 3 5
2 1 3
1 9 6
1 8 2
1 7 1
1 6 1
Copper
½
1387
870
7 00
5 99
5 3 1
4 8 1
4 4 3
4 1 2
3 8 6
3 6 5
Tubing
5/8
2360
1622
1303
1115
9 8 8
8 9 6
8 2 4
7 6 7
7 1 9
6 7 9
(O.D.)
¾
3993
2475
2205
1887
1672
1515
1394
1297
1217
1149
½
3339
2295
1843
1577
1398
1267
1165
1084
1017
9 6 1
Pipe
¾
6982
4799
3854
3298
2923
2649
2437
2267
2127
2009
Size
1
13153
9040
7259
6213
5507
4989
4590
4270
4007
3785
1-1/4
27004
18560
14904
12756
11306
10244
9424
8767
8226
7770
1-1/2
40461
27809
22331
19113
16939
15348
14120
13136
12325
11642
2
77924
53556
43008
36809
32623
29559
27194
25299
23737
22422
12 5
150
1 75
2 00
2 2 5
2 5 0
2 7 5
3 0 0
3 5 0
4 0 0
3/8
1 42
1 30
11 8
111
1 0 4
9 0
8 9
8 9
8 2
7 6
Copper
½
32 3
293
2 69
2 51
235
222
2 1 1
2 0 1
1 85
1 7 2
Tubing
5/8
6 01
5 46
50 2
467
4 3 8
4 1 4
3 9 3
3 7 5
3 4 5
3 2 1
(O.D.)
¾
1018
923
8 43
7 90
7 4 0
7 0 0
6 6 4
6 3 4
5 8 4
5 4 3
½
85 2
772
7 10
6 60
6 1 9
5 8 5
5 5 6
5 3 0
4 8 8
4 5 4
Pipe
¾
1780
1613
1484
1381
1296
1224
1162
1109
1020
9 4 9
Size
1
3354
3039
2796
2601
2441
2305
2190
2089
1922
1788
1-1/4
6887
6240
5741
5340
5011
4733
4495
4289
3945
3670
1-1/2
10318
9349
8601
8002
7508
7092
6735
6426
5911
5499
2
19871
18005
16564
15410
14459
13658
12971
12375
11385
10591
*Total length of piping from outlet of first stage regulator to inlet of second stage regulator (or to inlet of second stage regulator furthest
away).
Notes:
1) To allow 2 PSIG pressure drop, multiply total gas demand by .707, and use capacities from table.
2 )
For different first stage pressures, multiply total gas demand by the following factors, and use capacities from table.
First State Pressure PSIG Multiply by
2 0
.844
2 1
.912
Data Calculated per NFPA #54 & 58.
TABLE 4 – Second, Single, or Integral Twin Stage Pipe Sizing
11 Inches Water Column Inlet with a ½ Inch Water Column Drop
Maximum capacity of pipe or tubing in thousands of BTU/hr of LP-Gas
Size of Pipe
LENGTH OF PIPE OR TUBING, FEET*
Or Copper
Tubing, Inches
1 0
2 0
3 0
4 0
5 0
6 0
7 0
8 0
9 0
1 0 0
3/8
4 9
3 4
2 7
2 3
2 0
1 9
—
—
—
—
Copper
1/2
1 1 0
7 6
6 1
5 2
4 6
4 2
3 8
3 6
3 3
3 2
Tubing
5/8
2 06
1 41
11 4
9 7
8 6
7 8
7 1
6 7
6 2
5 9
(O.D.)
3/4
3 4 8
2 3 9
1 9 2
1 6 4
146
132
1 2 0
1 1 3
1 0 5
1 0 0
7/8
53 6
36 8
29 6
253
2 2 4
2 0 3
1 8 5
1 7 4
1 6 1
1 5 4
1/2
29 1
20 0
16 1
137
1 2 2
1 1 0
1 0 2
9 4
8 7
8 4
Pipe
3/4
60 8
41 8
33 6
287
2 5 5
2 3 1
2 1 2
1 9 8
1 8 5
1 7 5
Size
1
1146
788
6 32
54 1
4 8 0
4 3 5
4 0 0
3 7 2
3 4 9
3 3 0
1-1/4
2353
1617
1299
1111
9 8 5
8 9 2
8 2 1
7 6 4
7 1 7
6 7 7
1-1/2
3525
2423
1946
1665
1476
1337
1230
1144
1074
1014
2
6789
4666
3747
3207
2842
2575
2369
2204
2068
1954
12 5
150
1 75
20 0
2 2 5
2 5 0
2 7 5
3 0 0
3 5 0
4 0 0
3/8
—
—
—
—
—
—
—
—
—
—
Copper
1/2
—
—
—
—
—
—
—
—
—
—
Tubing
5/8
—
—
—
—
—
—
—
—
—
—
(O.D.)
3/4
—
—
—
—
—
—
—
—
—
—
7/8
—
—
—
—
—
—
—
—
—
—
1/2
7 4
6 7
6 2
5 8
5 4
5 1
4 8
4 6
4 3
4 0
Pipe
3/4
15 5
14 1
12 9
120
1 1 3
1 0 7
1 0 1
9 7
8 9
8 3
Size
1
2 9 2
26 5
244
2 27
2 1 3
2 0 1
1 9 1
1 8 2
1 6 7
1 5 6
1-1/4
6 0 0
54 4
50 0
465
437
412
3 9 2
37 4
34 4
3 20
1-1/2
89 9
81 5
74 9
697
654
618
5 8 7
56 0
51 5
4 79
2
1731
1569
1443
1343
1260
1190
1130
1078
9 9 2
9 2 3
*Total length of piping from outlet of regulator to appliance furthest away.
Data Calculated per NFPA #54 & 58.
Page 8
PROPANE GAS
PROPANE GAS