Powers PowerStation XP Single and Multi-Valve Series - Double Valve 0.5 - 271 gpm User Manual
Technical instructions

Description
n
Capacity
n
Two Valve PowerStation
™
Supply Fixture
Capacity up to 271 gpm @ 45psi
Technical Instructions
IS-P-SF-2VPS
Advanced Thermal Activation
Maximum Operating Pressure ............................. 125psi (861 kPa)
Maximum Hot Water Temperature ...................... 200°F (93°C)
Minimum Hot Water Supply Temp.* ................... 5°F (3°C) Above Set Point
Hot Water Inlet Temperature Range ................... 120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ................. 40 - 80°F (4 - 27°C)
Minimum Flow** ...................................................... 0.5 gpm (1.89 lpm)
Temp. Adjustment Range *** ............................... 90 - 160°F (32 - 71°C)
Listing/Compliance (Valve Only)............................ ASSE 1017, CSA B125
* With Equal Pressure
** Minimum flow when 2VPS is installed at or near hot water source recirculating tempered
water with a properly sized continuously operating recirculating pump.
*** Note: Low limit cannot be less than the cold water temperature. For best operation, hot
water should be at least 5°F (3°C) above desired set point.
Specifications
n
Flow Capacity at 50-50 Mixed Ratio
P r e s s u r e D r o p A c r o s s V a l v e
Model
Min. Flow
C
V
5psi
10psi
20psi
30psi
45psi
60psi
to ASSE 1017
(34 kPa)
(69 kPa)
(138 kPa)
(207 kPa)
(310 kPa)
(414 kPa)
MM431HL and
LFMM431HL
0.5 gpm
9.70
22 gpm
31 gpm
43 gpm
53 gpm
65 gpm
75 gpm
1.89 lpm
83 lpm
117 lpm
163 lpm
201 lpm
246 lpm
284 lpm
MM432HL and
LFMM432HL
0.5 gpm
13.00
29 gpm
41 gpm
58 gpm
66 gpm
87 gpm
93 gpm
1.89 lpm
110 lpm
155 lpm
220 lpm
250 lpm
329 lpm
352 lpm
MM433HL and
LFMM433HL
0.5 gpm
19.80
44 gpm
63 gpm
86 gpm
108 gpm
133 gpm
153 gpm
1.89 lpm
167 lpm
238 lpm
326 lpm
409 lpm
503 lpm
579 lpm
MM434HL and
LFMM434HL
0.5 gpm
24.90
56 gpm
79 gpm
111 gpm
136 gpm
167 gpm
193 gpm
1.89 lpm
212 lpm
299 lpm
420 lpm
515 lpm
632 lpm
731 lpm
MM435HL and
LFMM435HL
3.0 gpm
27.70
62 gpm
88 gpm
124 gpm
152 gpm
186 gpm
215 gpm
11.0 lpm
235 lpm
333 lpm
469 lpm
575 lpm
704 lpm
814 lpm
SH1432DV and
LFSH1432DV
2 gpm
27.40
61 gpm
87 gpm
123 gpm
150 gpm
184 gpm
213 gpm
8 lpm
231 lpm
329 lpm
466 lpm
568 lpm
697 lpm
806 lpm
SH1434DV and
LFSH1434DV
2 gpm
37.40
84 gpm
118 gpm
167 gpm
205 gpm
251 gpm
290 gpm
8 lpm
318 lpm
447 lpm
632 lpm
776 lpm
950 lpm
1098 lpm
SH1432HL and
LFSH1432HL
1 gpm
30.00
67 gpm
95 gpm
134 gpm
164 gpm
201 gpm
232 gpm
4 lpm
254 lpm
360 lpm
507 lpm
621 lpm
761 lpm
878 lpm
SH1434HL and
LFSH1434HL
1 gpm
40.40
90 gpm
128 gpm
181 gpm
221 gpm
271 gpm
313 gpm
4 lpm
341 lpm
485 lpm
685 lpm
837 lpm
1026 lpm
1185 lpm
WARNING: TO ENSURE THE
ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS
ESSENTIAL TO:
• Properly size each valve based on the indi-
vidual application.
• Properly design the recirculation system to
minimize pressure and temperature variations.
• Conduct an annual maintenance program to
ensure proper operation of all critical com-
ponents.
THIS VALVE MUST BE USED IN
CONJUNCTION WITH TEMPERATURE
ACTUATED POINT-OF-USE DEVICES THAT
COMPLY WITH ASSE 1016, 1069, OR 1070.
FAILURE TO COMPLY WITH PROPER
INSTALLATION INSTRUCTIONS COULD
CONTRIBUTE TO VALVE FAILURE, RESULTING
IN IN JURY OR DEATH.
!
Powerstation
™
is a complete, fully assembled water tempering system, designed to
provide safe water throughout commercial and institutional facilities. Powerstation
™
features the HydroGuard
®
LM490 or LFLM490, HydroGuard
®
XP MM430 or LFMM430,
and SH1430 or LFSH1430 Master Tempering Series valve which utilize paraffin-based
actuation technology to sense and to adjust outlet temperature. Each Powerstation
™
is mounted on heavy-duty, welded struts and factory tested as a complete system.
Each Powerstation
™
includes an engineer specified circulator, GFCI outlet, combination
temperature/pressure gauges and Powers' triple-duty checkstops. Optional equipment
includes an Aquastat and/or Powers' exclusive automatic balancing valve and a internal
bypass loop for and easy set-up.