MODEL KEFS LIQUID LEVEL FLOAT SWITCH

INSTALLATION / OPERATION INSTRUCTIONS


PRINCIPLE OF OPERATION
The Model KEFS uses a float to determine the presence or absence of liquid at the process connection. The float arm assembly
consists of a float at one end and a magnet at the other. As the level rises, the float rises, and the magnet falls. The magnet
actuates a second magnet on the other side of the pressure boundary. This second magnet causes the switch to change state.

The pressure boundary contains no seals; it is a solid stainless steel barrier that passes a magnetic field, but no liquids. It is
impossible for the process liquid to enter the switch enclosure through this barrier.

The electrical contacts consist of a microswitch that can be either a Single-pole, Double-throw (SPDT) or Double-pole, Double-throw
(DPDT) Configuration. The SPDT Switch is available with either a 5 Amp or 8 Amp current load. The DPDT is available with a 5
Amp/30Vdc current load (See Switch Types and Ratings in the Product Specifications for more details).


MODEL DESCRIPTION

KEFS - - - -


Process Connection

Switch Rating

Temperature Rating

Wetted Parts




* High

temperature option only available with 5A SPDT switch










(58639 Rev B)

Temperature Rating

Wetted Parts

Description

Code

Description

Code

Standard

blank

303 SS (std.)

blank

High* 400

316

SS S6

Process Connection Switch Rating

Description

Code

Description

Code

1½” NPT

N/A

5A SPDT

SPDT5

2” NPT (std.)

2

4A DPDT

DPDT4

8A

SPDT

SPDT8