beautypg.com

Harrington Signal ASHX-24SMR User Manual

Page 4

background image

Model ASHX PowerTone® Amplified Speaker for Hazardous Location

Document #256881

- 4 -

OPERATION/TESTING

WARNING

Under certain conditions these devices are capable of
producing sounds loud enough to cause hearing damage.
Adequate hearing protection should be worn if standing within
close proximity to device while testing. Recommendations in
the OSHA Sound Level Standard (29 CFR 1910) should not be
exceeded.

Property damage, serious injury, or death could occur if the
housing is not closed properly. To reduce possibility of
explosion, housing cover must be kept tight (all eight bolts fully
tightened) while circuits are energized.

After installation is complete, be sure to test the system to verify that
each amplified speaker operates satisfactorily. If it is found that the unit is
too loud for its location, an internal volume control can be adjusted.
Remove the housing cover and insert a slotted screwdriver with an 1/8"
blade into the hole shown in figure 2. Gently turn control to desired
loudness. Reinstall the housing cover.

After completion of initial system test, establish a program for periodic
testing of this device. Refer to NFPA 72, local Fire Codes and the
authority having jurisdiction for this information.

Provide a copy of these instructions for the Safety Engineer, system
operator(s) and maintenance personnel.

SAFETY MESSAGE TO OPERATORS

Even if your warning system is operating properly, it may not
be completely effective. People may not hear or heed your
warning signal. You must recognize this fact and ensure that
your warning signal achieves its intended effect through
proper

test/training

sequences

within

your

specific

application(s).

MAINTENANCE

SAFETY MESSAGE TO MAINTENANCE PERSONNEL

Failure to follow all safety precautions and instructions may
result in property damage, serious injury, or death to you or
others.

• Read and understand all instructions before performing maintenance

on this unit.

• Do not perform maintenance on this unit when circuits are energized.
• Periodic checks should be made to ensure that effectiveness of this

device has not been reduced because speaker has become clogged
with a foreign substance or because objects have been placed in front
of the speaker

290A2920

24 VDC

POWER

25 OR 7O

VRMS

AUDIO

END OF LINE DEVICE

RECOMMENDED BY

CONTROL UNIT SUPPLIER

POWER SUPERVISION

RELAY MODEL A77-716-02

BY SYSTEM SENSOR, OR

MODEL R64 BY UNITED
SECURITY PRODUCTS,

OR MODEL PAM-2,
BY AIR PRODUCTS

& CONTROL LTD.

WHT

WHT

WHT

WHT

WHT

WHT

WHT

WHT

RED

RED

BLK

BLK

RED

BLK

RED

BLK

(

+

)

(

-

)

INTERNAL PICK

CONNECTOR CARD

(25 OR 70 VRMS

SUPPLIED

SEPERATELY)

Figure 4: Typical connector card (PTCK) installation wiring

290A2627-14

RED

BLK

BLK

+

RED

+

-

RED

BLK

+

-

-

24VDC

POWER

SPEAKER

MODEL

ASHX

END OF LINE DEVICE

RECOMMENDED BY

CONTROL UNIT

SUPPLIER

Figure 3: Typical tone card installation wiring