beautypg.com

1 fuses, 2 checking the engine oil level, 3 changing the engine oil – Bryant ASPAX1BBA015 User Manual

Page 18: 3 overcrank, 1 approximate crank cycle times, 4 overspeed, 1 engine oil recommendations, Figure 4.1 – generator control panel, Figure 4.2 — oil dipstick and fill, 15 kw

background image

3.7.3 OVERCRANK

This feature prevents the generator from damaging
itself when it continually attempts to start and anoth-
er problem, such as no fuel supply, prevents it from
starting. The unit will crank and rest for a preset time
limit. Then, it will stop cranking, and the LED will
light indicating an overcrank failure. The AUTO/OFF/
MANUAL switch will need to be set to OFF and then
back to AUTO to reset the generator control board.

NOTE:

If the fault is not repaired, the overcrank feature
will continue to activate.

3.7.3.1 Approximate Crank Cycle Times

• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total

3.7.4 OVERSPEED

This feature protects the generator from damage by
shutting it down if it happens to run faster than the
preset limit. This protection also prevents the genera-
tor from supplying an output that could potentially
damage appliances connected to the generator cir-
cuit. Contact the nearest dealer if this failure occurs.

4.1 FUSES

The generator panel’s 15 amp fuse (Figure 4.1) pro-
tects the DC control circuit against overload. The fuse
is wired in series with the battery output lead to the
panel. If the fuse element has melted open, the engine
cannot crank or start. Replace the fuse using only an
identical 15-amp replacement.

The generator panel’s 7.5 amp fuse protects the 12
VDC accessory socket. If the fuse element has melted
open, the 12 VDC socket will not provide power to
any accessories. Replace the fuse using only an iden-
tical 7.5 amp replacement. To remove fuse, push the
fuse holder cap down and rotate counterclockwise.

Figure 4.1 – Generator Control Panel

12 VDC

ACCESSORY

OUTLET 7.5A MAX

EXERCISE

15A

SYSTEM FUSE

TIME

SET

AUTO

7.5A

OUTLET FUSE

OFF

MAN.

F L A S H IN G

G R E E N

L E D =

4

F L A S H IN G

R E D

L E D S =

N O

U T IL IT Y

S E N S E

E X E R C IS E R

N O T

S E T

OVER CRANK

LOW OIL

OVER SPEED

HIGH TEMP.

SYSTEM SET

EXTERNAL

CIRCUIT

BREAKER

GFCI

‹

‹

4.2

CHECKING THE ENGINE
OIL LEVEL

For oil capacities, see the “Specifications,” Section.
For engine oil recommendations, see Section 4.3.1.
To check the engine oil level, proceed as follows
(Figure 4.2):

1. Start the generator by moving the AUTO/OFF/

MANUAL switch to the MANUAL position. Allow
it to run for a short while and then shut it down
by moving the switch to the OFF position.

2. Remove the dipstick and wipe it dry with a clean

cloth.

3. Install the dipstick; then, remove it again. The oil

level should be at the dipstick “Full” mark. If nec-
essary, add oil to the “Full” mark only. DO NOT
FILL ABOVE THE “FULL” MARK.

Never operate the engine with the oil level

below the “Add” mark on the dipstick. Doing
this could damage the engine.

4. Install

the

dipstick.

5. Reset the AUTO/OFF/MANUAL switch to its origi-

nal position.

Figure 4.2 — Oil Dipstick and Fill, 15 kW

Oil Dipstick

Oil Fill

4.3 CHANGING THE ENGINE OIL

4.3.1 ENGINE OIL RECOMMENDATIONS

Use oil of American Petroleum Institute (API) Service
Class SG, SH or SJ. Use all season SAE 5W-30
Synthetic oil. Organic break-in oil is required before
using synthetic oil.

NOTE:

The unit is supplied with “break-in” oil. See the
“Break-in Procedure” Section for the first required
oil change.

‹

16

Section 4 — Maintenance

15 kW Generator