12

SW1

Input voltage

1

2

3

4

5

6

7

8

9

10

0...10 mV

0

0

0

0

0...20 mV

0

0

0

1

0...50 mV

0

0

1

0

0...100 mV

0

0

1

1

0...200 mV

0

1

0

0

0...500 mV

0

1

0

1

-10 mV...10 mV

1

0

0

0

-20 mV...20 mV

1

0

0

1

-50 mV...50 mV

1

0

1

0

-100 mV...100 mV

1

0

1

1

-200 mV...200 mV

1

1

0

0

-500 mV...500 mV

1

1

0

1

Output
0...+10 V

0

0

0...+ 5 V

0

1

0...20 mA

1

0

4...20 mA

1

1

Supply voltage to the bridge
+10 V

1

0

0

+ 5 V

1

0

1

+4,8...+10,2 V adjustable

0

1

0

+4,8...+10,2 V adjustable

0

1

1

and offset is also adjustable
Response
Standard output signals

0

Inverse output signals

1

0= open, 1= closed