Det-Tronics OPECL Infrared Hydrocarbon Gas Detector SAFETY MANUAL User Manual

Det-Tronics Equipment

background image

SAFETY MANUAL

Infrared Hydrocarbon Gas Detector

Open Path Eclipse

SIL 2 Certified Model OPECL

1.2

©

Detector Electronics Corporation 2011

4/11 95-8665

SAFETY CERTIFIED MODEL OPECL
OPEN PATH ECLIPSE IR GAS DETECTOR
This manual addresses the specific requirements and

recommendations applicable to the proper installation,

operation, and maintenance of all Safety-Certified

(SIL-Certified) Model OPECL Open Path Eclipse IR Gas

Detector product versions. For complete information

regarding system overview, performance, installation

(including alignment), operation, maintenance and

specifications of the Model OPECL, refer to instruction

manual 95-8556.

QUALITY POLICY STATEMENT
All quality assurance control measures necessary for

safety management as specified in IEC 61508 Part 1

have been implemented. The quality management

system of Det-Tronics is based on the requirements

of EN ISO 9001 and ANSI/ASQC Q9001 through the

application of the United Technologies Company

Achieving Competitive Excellence (ACE) program. In

addition, the Quality Management System complies

with the European ATEX Directive requirements per EN

13980, the International Electrotechnical Commission

requirements per OD005/V2, and the supervised

testing requirements per ISO 17025.

SAFETY MESSAGES
Procedures and instructions in this section may

require special precautions to ensure the safety of

personnel performing the operations. Information that

raises potential safety issues is indicated by the word

“Warning”. Always read and understand these safety

messages.

WARNING

The Model OPECL Gas Detector is intended for
use in hazardous environments that may include
explosive levels of flammable gases and vapors.
This product must be properly installed, operated
and maintained. Improper installation or use
could result in an explosion or fire resulting in
death or serious injury.
• Do not remove the wiring compartment cover

in explosive environments when device power
is on and circuits are live.

• Detector must be properly installed, and wiring

compartment cover must be fully engaged
to meet hazardous area explosion-proof/
non-incendive requirements.

• Before connecting a HART field communicator

to the OPECL Open Path IR Gas Detector in
a potentially explosive atmosphere, make
sure the field communicator is suitable and
approved for use in the specific area.