A.) CLEANING

Washing and cleaning of Flow / Con fabric air diffusers should be carried out in accordance with the following
instructions.

1.)

Hand or power wash with clean water @ max. 140` F. Diffusers made of polyester may be machined washed
(if diffusers are in small enough sections).

2.)

If the diffusers are heavily soiled, use mild laundry detergent in accordance with manufacturer’s instructions.
(repeat if necessary)

3.)

After washing, rinse with clean cold water.

4.)

Do not dry in dryer, hang dry.

Because Flow Con diffusers are laundered so infrequently, extremely soiled diffusers will require laundering more
than once. In our experience we suggest contacting a local industrial laundering service equipped with industrial
laundering equipment to clean the diffusers properly.

B.) REPAIR

Consult your sales representative first in order to determine if the diffuser can be repaired on site or if it has to be sent
back to the factory. Patch kits are available.

B1) Polyethylene and Vinyl

1.) Clean the surface of the Flow Con fabric air diffuser that needs repair in accordance with the above

instructions.

2.) For tears longer than eight inches cut a patch 1 to 2 inches longer and wider than patch.

3.) Apply the repair tape to fabric and smooth out any air bubbles by smoothing to the edge of patch.

4.) Wait 5 minutes before turning unit back on.

B2) Polyester (similar to above)

1.) Clean the surface of the Flow Con fabric air diffuser that needs repair in accordance with the above

instructions.

2.) For tears longer than eight inches cut a patch 1 to 2 inches longer and wider than patch.

3.) Apply the adhesive to fabric and smooth out any air bubbles by smoothing to the edge of patch.

4.) Wait 15 minutes before turning unit back on.