beautypg.com

Pathway DMX Relay Controller (standard version) - # LCRC48GE User Manual

Lcrc48ge dmx relay controller configuration, Installation instructions, Dip switch settings

background image

LCRC48GE DMX RELAY CONTROLLER Configuration

INSTALLATION INSTRUCTIONS

1 - Ensure that relay panel power is off (no indicator LEDs

glowing on the system motherboard). Remove the metal
cardframe cover.

2 - Connect the DMX data line at the panel motherboard, with

D- to the black terminal and D+ to the red terminal. Attach
the shield drain wire to the SHIELD terminal.

3 - If the DMX line is to be passed through to another panel,

attach the outgoing wires to the second set of data
terminals.

4 - If the relay panel is the last panel on the DMX wire run, it is

recommended that a 100 or 120 ohm 1/4W termination
resistor be installed between one pair of black and red data
line terminals.

5 - Configure the controller card according to the following DIP

switch settings.

6 - Plug the LCRC-48 controller card and one to four LCRD-

12 driver cards firmly into the cardframe. Restore power.

7 - Check that the power LED (between the DIP switch and the

three rotary switches) is glowing steadily. This indicates +5
volts present and correct microprocessor operation. A
flashing LED indicates a defective controller card.

8 - Set the 3 rotary address switches to the dimmer number

corresponding to the first relay in the panel. Note that
“000” (the factory default address) and “001” are
equivalent.

9 - Apply the DMX control signal and observe that the receive

data LED (at left) is glowing. The LED will not glow if the
address set on the rotary switches exceeds either 512 or
the number of dimmer signals present on the data line, if
the data format does not conform to USITT-DMX512, or if
the data wires are reversed at the mother board.

10- Verify relay operation with the DMX control system or using

the card's test function. Ensure that everything is set
correctly before re-installing the cardframe cover.

THRESHOLD SELECT

DS-1

DS-2

20% THRESHOLD (Trigger on at 25%, off at 15%)

ON

ON

40% THRESHOLD (Trigger on at 45%, off at 35%)

OFF

ON

60% THRESHOLD (Trigger on at 65%, off at 55%)

ON

OFF

80% THRESHOLD (Trigger on at 85%, off at 75%)

OFF

OFF

RELAY SELECTION

DS-3

DS-4

1-12 RELAYS INSTALLED

ON

ON

13-24 RELAYS INSTALLED

OFF

ON

25-36 RELAYS INSTALLED

ON

OFF

37-48 RELAYS INSTALLED

OFF

OFF

RESERVED FOR FUTURE USE

DS-5

RESERVED FOR FUTURE USE

DS-6

DIP Switch Settings

SCAN RATE

DS-7

FAST SCAN (50 msec., 20 relays per second)

ON

NORMAL SCAN (100 msec., 10 relays per second)

OFF

TEST MODE

DS-8

Test Mode enabled

ON

Normal (RUN) Mode

OFF

3.

7

0

00

"

10.3000"

RxD x100

x10

x1

PWR

DS

When test mode enabled, relays are turned on one at a time as
selected by the rotary address switches

NOTE RE: GROUNDING

Pay particular attention to the grounding of the data line shield.
If the DMX controller grounds the shield, that is sufficient. If not,
a jumper wire must be installed between the data line SHIELD
terminal and the relay panel COM terminal. Only one such
ground connection should be made in any one data cable run.

05/03

Printed in Canada

[email protected]

www.pathwayconnect.com

Pathway Connectivity Inc., 480C - 36 Avenue S.E.,

Calgary, AB, T2G 1W4 Canada
tel (403) 243-8110 fax (403) 287-1281