Safety Precautions

Both the installer and the owner and/or operator of the operator panel must read and
understand this installation manual.

1.1 UL and cUL Installation

– This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D

OR non-hazardous locations only. [Combinations of equipment in your system
are subject to investigation by the local Authority Having Jurisdiction at the time
of installation.]

– Maximum ambient temperature 40 °C when mounted horizontal or 50 °C when

mounted vertical.

– WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless

power has been removed or the area is known to be non-hazardous.

– For Canada also AVERTISSEMENT – RISQUE D’EXPLOSION – AVANT DE

DECONNECTER L’EQUIPEMENT, COUPER LE COURANT OU
S’ASSURER QUE L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.

– WARNING – EXPLOSION HAZARD - Substitution of components may

impair suitability for Class I, Division 2.

– For Canada also AVERTISSEMENT – RISQUE D’EXPLOSION – LA

SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIEL
INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I,
DIVISION 2.

– WARNING – EXPLOSION HAZARD – only UL and cUL approved expansion

units are allowed to be connected to the port designated “EXPANSION”. At the
moment there are no such units evaluated or allowed.

– WARNING – EXPLOSION HAZARD - Do not replace expansion unit unless

power has been switched off or the area is known to be non-hazardous.

– This product contains battery, this must only be changed in an area known to be

non-hazardous. Permitted types are shown in the section

Technical Data

.

– For use on a flat surface of a type 4X enclosure indoor use only.

– To make wiring connections to the power supply connector, use an AWG 28-12

cable and a tightening torque of min. 0.5 Nm.