beautypg.com

Beijer Electronics iX T4A EN User Manual

Page 5

background image

Safety Precautions

All devices have to be supplied by a Class 2 power supply.

Warning:
Do not disconnect equipment unless power has been removed or the area is
known to be non-hazardous

For Canada also AVERTISSEMENT – AVANT DE DECONNECTER
L’EQUIPEMENT, COUPER LE COURANT OUS’ASSURER QUE
L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.

Warning:
Only UL and cUL approved expansion units are allowed to be connected to
the port designated “EXPANSION”. At the moment there are no such units
evaluated or allowed.

Warning:
Do not replace expansion unit unless power has been switched off or the area
is known to be non-hazardous.

This product contains a battery; this must only be changed in an area known
to be non-hazardous.

Replace the battery with a BR 2032 battery. Use of another type of battery
may present a risk of fire or explosion.

Warning:
Battery may explode if mistreated. Do not recharge, disassemble or dispose
of in fire.

For use on a flat surface of a type 4X enclosure indoor use only.

Use 75 degree conductors only

Use copper conductors only

To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:

Terminal Block No.

Wire Size AWG

TQ Lb.In.

X1/X100 Phoenix connectors

AWG 30–12

5–7

X1/X100 Anytek connectors

AWG 24–12

3.5

These devices are Class 2 supplied programmable controllers (industrial PCs)
for the use in industrial control equipment and are intended to be (front)
panel mounted (Type 1 and 4x for indoor use only).

Beijer Electronics, MAEN015F

5