(3) Serial Communication Error Identification Procedure

Refer to "Method of Self-Diagnostics" for the self-diagnostics procedure.

(3-1) Condition: E01

< Before the Operation >

If the lamps on the main body show the following conditions after the completion of self-diagnostics,

a communication error between the indoor unit and outdoor unit might be considered.

In such a case, identify the breakdown section by using the following procedure.

Troubleshooting Serial Communication

Is the voltage of about DC12V

or more given between the terminals

2 and 3 on the outdoor unit terminal strip

(Serial Communication Line) ?

(Fig. 1)

No

Yes

1. Turn OFF the power and wait until the power lamp (LED)
of the outdoor unit controller is turned OFF.
2. Disconnect the cable from the terminal 3 on the indoor unit
terminal strip. (Fig. 2)
3. Turn ON the power.

< Convenient Tool for Short-Circuit Work ( for example ) >

Alligator Clip

Alligator Clip

Cable

A

( Continued to the next page A. )

B

( Continued to the next page B. )

For terminal strip short circuit work or inter-unit wiring removal, turn off the power to
avoid an electric shock.
Release the terminal strip short circuit after the completion of self-diagnostics.

Do not perform the short-circuit work between any other terminals except for
specified ones on the specified terminal strip. If such work is performed between
the incorrect terminals, the unit might be broken.

Fig. 1

Outdoor Unit

Power

1

2

4

3

5

6

1

2

3

V

+

-

Indoor Unit

Outdoor Unit

1

2

4

3

5

6

1

2

3

V

+

-

Power

Indoor Unit

Fig. 2

NOTE

: Off

: Blinking

: Illuminated

CAUTION

WARNING

< Check Items before Troubleshooting Serial Communication Start >

After confirming that the following errors do not exist, start the "Troubleshooting Serial Communication"
in "Condition: E01 and E12".

1. Mis -wiring (inter-unit cable, etc.)
2. AC power failure
3. Blown

fuse

4. Power Relay failure
5. Outdoor Fan Motor failure (defective insulation, etc.)

6. Reactor failure (defective insulation, etc.)
7. High-Pressure Switch failure
8. Overload Relay failure
9. Magnetic Coil failure (defective insulation, short-circuit, etc.)
10. Compressor failure (defective insulation, etc.)