Error Messages
14
*
LED flash
Lo – Low Tone
Hi – High Tone
Beep / Flash Sequence
What it means
What to do
During Power up
LoHi-LoHi-LoHi
Indicates Battery Lift is open
No action required
during power up
Long Tone
Indicates start of power up test
No action required
Lo – Lo – Lo
No Dip Switch has been selected
No action required
Hi – Lo – Lo
Dip Switch 1 has been selected
No action required
Lo – Hi – Lo
Dip Switch 2 has been selected
No action required
Hi – Hi – Lo
Dip Switches 1 and 2
No action required
have been selected
Lo – Lo – Hi
Dip Switch 3 has been selected
No action required
Hi – Lo – Hi
Dip Switches 1 and 3
No action required
have been selected
Lo – Hi – Hi
Dip Switches 2 and 3
No action required
have been selected
Hi – Hi – Hi
Dip Switches 1, 2 and 3
No action required
have been selected
Dip Switch 4 has no function and
will not affect beep sequence
During standard operation
*
---(32secs)---
*
---(32secs)---
*
---(32secs)---
*
---etc.
LED indicates that the system is
No action required
working properly
*
-(1.3secs)-
*
-(1.3secs)-
*
-(1.3secs)-
*
-(1.3secs)-
*
-etc
LED indicates that the Dorgard
If no alarm is sounding
is “hearing” a possible alarm (or a please refer to the
continuous background noise
section on adjusting
in excess of 65 decibels)
the sensitivity of
Dorgard.
HiLo – HiLo – HiLo – HiLo – HiLo – HiLo – HiLo – HiLo
Dorgard is about to release door
No action required
*
-------
*
-------
*
-------
*
-------
*
-------
*
-------
*
-------
*
(If warning tone has been