beautypg.com

Dwyer CCS User Manual

Dwyer instruments, inc, Series ccs current switches, Bulletin pc-ccs

background image

Series CCS Current Switches

Specifications - Installation and Operating Instructions

Bulletin PC-CCS

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057

e-mail: [email protected]

2-7/16

[62.00]

55/64

[22.00]

SPLIT MODELS

4-1/64

[102.00]

SOLID MODELS

55/64

[22.00]

2-3/4

[70.00]

2-33/64

[64.00]

19/32

[15.00]

43/64

[17.00]

2X

Ш13/64

[Ш5.00]

3-1/2

[89.00]

1-17/64

[32.00]

2X Ш13/64

[Ш5.00]

45/64

[18.00]

33/64

[13.00]

2-31/64

[63.00]

33/64

[13.00]

63/64

[25.00]

2-29/32

[74.00]

3-1/2

[89.00]

55/64

[22.00]

1-9/64

[29.00]

Ш3/4

[Ш19.00]

The Series CCS Current Switches are ideal for monitoring the operating status of

fans, pumps, and motors. These self-powered switches can be hung or tied directly

to cables or wires. For use on existing installations, split core models can be

installed without disconnecting cables. LED indicators provide a visual

confirmation that the current is flowing through the core. Both fixed and adjustable

set points are available. The adjustable models utilize a potentiometer to easily

adjust the set point.

OPERATING INSTRUCTIONS

The Series CCS Current Switches are intended to provide an

input to equipment under normal operating conditions. Where

failure or malfunction of the current switch could lead to personal injury or property

damage to the controlled equipment or other property, additional precautions, must

be designed into the control system. Incorporate and maintain other devices such

as supervisory or alarm systems or safety or limit controls intended to warn of, or

protect against, failure or malfunction of the CCS.

RISK OF SHOCK

Disconnect power supply before making electrical connections.

Contact with components carrying hazardous voltage can

cause electrical shock and may result in severe personal injury or death.

INSTALLATION

MOUNTING

1. Mount the switch in a suitable location using the two mounting holes in the base

of the unit.

2. If using ties, make sure ties are securely fastened and that the unit is stable.

If using the provided screws, tightly screw in one screw at a time into each hole.

WIRING

1. Ensure that the power supply to the circuit is off.

2. For solid core devices: disconnect the circuit line, slide the power conductor

cable through the sensing hole of the current switch, and reconnect the circuit

line.

For split core devices: open the core using the release tab. Snap the core

closed around the power conductor cable. Make sure that the core release tab

is locked in its original position.

3. Connect the switch circuit to the two screw terminals using ring or fork type

terminals.

4. Turn circuit back on.

NOTICE

SPECIFICATIONS

Amperage Range: 0 to 200 A AC.

Maximum Switch Rating:

For dry contact models: 0.3 A @ 135VAC/DC;

For non-dry contact models: 1 A @ 240VAC.

Power Requirements: None, self-powered.

Operating Temperature: -22 to 158ºF (-30 to 70ºC).

Operating Humidity: 0 to 95% (non-condensing).

Isolation Voltage: 2000V.

Frequency: 40 to 400Hz.

Enclosure Rating: UL, 94 V-O flammability rated, ABS plastic housing.

Approvals: CE, UL.

LED INDICATORS

Green LED: indicates that current is passing through the core, but the set point

has not been reached and the contacts are open.

Red LED: indicates that the set point has been reached and the contacts are now

closed.

WARNING