SPECIFICATIONS
Inputs:
0 to 200 mVDC, 0 to 5 VDC, or 0 to 10 VDC.
Input Impedance: 390KΩ nominal.
Accuracy: ±(0.1% FS +2 count).
Power Supply: 12 VDC or 24 VDC.
Backlight Power Supply: 24 VDC @ 35 mA typical.
Span and Zero: Adjustable (±1999 counts).
Display: 3-1/2 digits, 7 segments, 0.45˝ (11.4 mm) H.
Decimal Points: 3-position, user selectable.
Engineering Units: DPMP-XXX: ºF, ºC, PSI; DPMP-XXXP: V, A, KW,
PF.
Polarity: Automatic, “-” displayed.
Operating Temperature: 32 to 122ºF (0 to 50ºC).
Storage Temperature: -4 to 158ºF (-20 to 70ºC).
Mounting: Snap-in bezel mounts.
Connection: Screw terminal.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 2 oz (56.7 g).
Agency Approvals: RoHS.

The DPMP-5 LCD Digital Panel Meter provides easy viewing on the 3-
1/2 digit display. The display segments are available in a choice of
amber, green or red. The meter features user selectable engineering
units, adjustable zero and span, and field selectable decimal point
position. The snap-in bezel mount eliminates mounting hardware.

INSTALLATION
The Series DPMP-5 is designed for panel mounting in a 2.4” x 1” (61 mm
x 25.1 mm) H panel cutout.

WIRING

The unit is powered by 12 or 24 VDC and the screw terminals for wiring
are located on the back of the adder board marked with “+ PWR -”. Move
the power select jumper for the appropriate power supply value (see
Figure 2). The backlighting requires a 24 VDC power supply and should
be connected to terminals identified with “+ B/L -”.

P Models

°F

°C

PSI

%

V

A

KW

PF

1/8

[3]

1-5/8

[41.1]

63/64

[25.1]

2-35/64

[64.5]

1-9/64

[29]

2-13/32

[61]

2.390 REAR HOUSING

[60.6]

1

[25.4]

PANEL CUTOUT FOR

WINDOW MOUNTING

Figure 1

Figure 2

The unit accepts 200 mVDC, 5 VDC or 10 VDC. Wire input according to
the figure below. Set the signal select jumper for the appropriate input.