Yokogawa Standalone MW100 User Manual

Page 10

background image

3. The ―RS Who‖ window will open showing current running drivers. In this example, there is an Ethernet driver

entitled ―AB_ETH

-1, Ethernet‖. Click on the ―+‖ symbol to the left of the driver. In the right window, connected

devices are shown.

4. Any devices connected to the ―AB_ETH

-1, Ethernet‖ driver now appear in the driver’s tree. In this example, there is a

Compact Logix processor located at IP address 192.168.1.95. For the DX Advanced or MW100 to be used as an

EtherNet IP device communicating to a Rockwell processor, the DX Advanced or MW100 must be mapped to an Ethernet

driver in RSLinx. An existing driver such as the ―AB_ETH-1, Ethernet‖ below may be used or a new driver created. For

this example, we are going to create a new driver in the next step.

7