beautypg.com

Bell & Gossett V58046B Wafer Valve Automatic Flow-Limiting Valve User Manual

Wafer valve automatic flow-limiting valve, Instruction manual

background image

DESCRIPTION

The Bell & Gossett WAFER Valve is designed to fit between

two 150 lb. ASME flanges and to automatically control the

flow in a piping system to a selected preset flow requirement.

As pressure differential increases, a cartridge inside the valve

body reduces the flow area to accurately maintain the pre-

selected flow rate.

Operational Limits

Maximum Operating Temperature: 250ºF (121ºC)

Maximum Operating Pressure: 250 psig (1724 kPa)

Flow Control, Differential Pressure:

2 to 60 psig (14 to 414 kPa) nominal

INSTALLATION INSTRUCTIONS

1. For installing Wafer Valves:

a) Install the Wafer valve in the piping system/circuit

where it is desired to maintain the flow at a pre-

selected value. The lifting lug (eye-bolt) provided (from

4" thru 20") will make handling of the valve easier.

Install the lifting lug into the valve body. Install

between two identical 150 lb. ASME flanges. Use long

threaded rods to connect the two flanges together

and secure the wafer valve and mating gasket in full

contact with the flanges. Torque each nut on the

threaded rod to specified torque value necessary for

typical flange torque connections.

b) Install the unit so that the flow arrow on the body

housing points in the direction of flow.

WARNING LABEL PART NO. V56871

INSTALLED IN THIS LOCATION (UNDER

BELL & GOSSETT). IF MISSING IT MUST

BE REPLACED.

SAFETY

INSTRUCTION

This safety alert symbol will be used in this manual to draw

attention to safety related instructions. When used, the safety

alert symbol means

ATTENTION! BECOME ALERT! YOUR

SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE IN-

STRUCTIONS MAY RESULT IN A SAFETY HAZARD.

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

CAUTION: Use unit lifting eyes only to lift unit as

shipped from factory. Unit must be empty and

disconnected from pipe, and other restraints. Use proper

rigging procedures. Failure to follow these instructions

could result in injury or property damage.

Wafer Valve

Automatic Flow-Limiting Valve

INSTRUCTION MANUAL

V58046B