F03 DISPLAY OR SET BATTERY TEMPERATURE
If there is no external temp sensor and F16 is OFF (factory default),
this function sets ambient battery temperature used to caluculate rate
corrected battery capacity which drives the LED bar graph and the
Time remaining display. Feature not available on units with serial
numbers prior to 05000.
DEFAULT: 20 °C
RANGE: 0–40 °C
STEP: 1 °C
If F16 is ON and an optional external temperature sensor is connected
between Pin 6 and Pin 8 (ground), F03 will display temperature
(0–99 °C). Temperature will continue to be displayed until one of the
two front panel buttons is pressed. Active Temperature display is
annunciated by the absence of front panel status indicators. If 0 is
displayed at normal (~ 20 °C) temperatures, an open temperature
probe should be assumed. If >99 is displayed at normal temperatures,
a shorted probe should be suspected.
F04 TURN ON KWHRS DISPLAY
Kilowatt hours are displayed in the Ah mode. (Note: The kWh display
does not take into account Charging Efficiency. As a condition for a
recalculation of the CEF and an automatic reset of amp hours to zero,
100% of the energy removed from the battery must be returned. The
number in the kWh display must be zero or positive to allow a
recalculation of the CEF and an automatic reset to zero. You may use
this function to verify that this condition has been met.)
DEFAULT: OFF
RANGE: OFF or ON
F05 USE ALTERNATIVE ENERGY (AE) DEFAULTS
Changes time to meet Charged Parameters to one minute from the
normal five minutes. (Also consider changing Charged Current to 4%.)
DEFAULT: OFF
RANGE: OFF or ON