Klinkmann Automation Omron Ethernet DAServer
58
 
 
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3 17014m13
number too large.
number below the 
maximum node number. 
03
Send error caused by 
lack of available space 
in PLC internal buffers. 
Reduce the traffic on the 
Ethernet Unit. Check 
user application. 
DASProtFail
05
Node number setting 
error. 
Make sure the node 
number is within 
specified range and that 
there are no duplicate 
node numbers. 
DASProtFail
06
Node number 
duplication error. 
Make sure that there are 
no duplicate node 
numbers. 
DASProtFail
02: Remote 
node error 
01
IP address of remote 
node was not set 
correctly in IP address 
table or IP router table. 
Set IP address of remote 
node into IP address 
table, and, if 
internetwork 
transmission is required, 
into IP router table. 
DASProtFail
02
No node with the 
specified unit address. 
Check the remote 
node’s unit address and 
make sure the correct 
one is being used in the 
control data. 
DASProtFail
05
Message packet was 
corrupted by 
transmission error or 
response time-out 
(response watchdog 
timer interval too short) 
or transmission frame 
corrupted or PLC 
internal reception buffer 
full. 
Check the protocol and 
controller status by 
reading them with FINS 
commands. Increase the 
number of transmit retry 
attempts. 
Increase the value for 
the response monitor 
time in the control data. 
Read out the error log 
and correct as required. 
DASProtFail
03: 
Communic. 
Controller 
error 
01
Error occured in the 
communications 
controler. ERC 
indicator is lit. 
Take corrective action, 
referring to 
troubleshooting 
procedures in PLC 
manual. 
DASProtFail
02
CPU error occured in 
the PC at the 
destination node. 
Check the CPU 
indicators at remote PLC 
and clear the error in the 
CPU (refer to the PLC’s 
DASProtFail