Installation, Installation example: class a chimney retrofit, For qualified installers only) – Lopi Horizontal Or Vertical Vent Freestanding Stove Yankee Pellet Stove User Manual
Page 15: Travis industries
![background image](/manuals/168114/15/background.png)
Installation
(For Qualified Installers Only)
1 5
Travis Industries
4050418
1 0 0 - 0 1 1 5 6
Installation Example: Class A Chimney Retrofit
Type "L" Vent
6” Minimum
3”
Minimum
Floor Protection
2”
Minimum
9” Minimum
“Tee”
Outside
Air
(optional)
Floor Protection
Outside air may be drawn from
a ventilated crawl space.
2” Min.
3” Min.
Class A Chimney Ceiling Support
Roof Flashing
“L” Vent to Class A Chimney Adapter
Class A Chimney
“L” Vent
Storm Collar
Class A Chimney must
maintain clearances outlined
in the chimney’s installation
instructions (usually 2”).
Seal each vent
section (including
adapters, elbows,
etc...) by injecting a
liberal amount of
500° F. RTV
silicone into the gap
between sections.
500
° F. RTV
Silicone