System Sensor 2100AT User Manual
System Sensor Safety
D200-69-00
1
I56-1145-05R
2100AT Photoelectronic
Smoke Detector with Fixed Heat
and Integral Temp-3 Sounder
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Diameter:
5.5 inches (140 mm)
Height (including mounting bracket):
2.05 inches (52 mm)
Weight:
7.5 oz. (210 g)
Operating Temperature Range
32
°
to 100
°
F (0
°
to 38
°
C)
Operating Humidity Range:
10% to 93% Relative Humidity, Noncondensing
Latching Alarm:
Reset by momentary power interruption
Audible Signal:
85 dBA minimum when in alarm or with supply polarity reversed
Heat Sensor:
135
°
F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage (nominal):
12 or 24 VDC
Minimum:
8.5 VDC
Maximum:
35 VDC
Maximum Ripple Voltage:
30% of nom. Voltage (peak to peak)
Standby Current:
50
µ
A average, 100
µ
A maximum
Alarm Ratings:
29 mA typical at 12 VDC, 63 mA typical at 24 VDC, 100 mA maximum
(If used, the RA400Z Remote Annunciator operates within the specified detector
alarm currents.)
Reset Voltage:
1.8 VDC minimum
Reset Time:
0.6 seconds maximum
Start-up Time:
30 seconds maximum (after 60 sec. reset)
EOL Relay:
A77-716B, 12/24 VDC
Special Considerations:
NOTE: Only one detector per zone shall be used, unless when in alarm the panel
switches the zone to a reverse polarity, non-current limited power supply. For
panels that do not provide this feature, a reversing relay, such as System Sensor’s
RR-2, may be used. When utilized with the 2100AT, it allows for more than one de-
tector to be utilized on a loop. Some panels may require the use of programmable
outputs. Refer to System Sensor literature for further information on the RR-2.
The 2100AT detector shall not be mixed with other 2-wire detectors on the same
zone.
–Due to the built-in temporal pattern, use this detector only with a non-coded
power source.
Figure 1. Wiring diagram for the 2100AT detector:
A78-2336-15
IMPORTANT: OBSERVE POLARITY
Polarity must be observed on the power and remote annunciator connections.
OPTIONAL CLASS A WIRING
EOL
INITIATING
LOOP
UL LISTED
COMPATIBLE
CONTROL
PANEL
+
–
+
+
–
A
+
RA400Z
REMOTE
ANNUNCIATOR
A
-
+
–
P
W
R
NOT
USED
NOTE: Only one detector per zone shall be used, unless when in alarm the panel switches
the zone to a reverse polarity, noncurrent-limited power supply. The 2100AT
detector shall not be mixed with other 2-wire detector types on the same zone.