4. Personalisation using external software

Main-output personalisation

Voltage-threshold personalisation

(1) Low threshold for transfer to battery is 150 V.

UPS-sensitivity personalisation

UPS ON/OFF personalisation

Battery personalisation

Insert the Solution-Pac CD-ROM in the drive.

On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal

Solution-Pac software.

Then select "Settings", "Advanced settings" and "UPS settings".

Note that the Linux/Unix/MacOS versions of Personal Solution-Pac software do not offer this possibility.
It is possible to modify the settings listed below (detailed comments are available in the Personal Solution-Pac software).

Function

Factory setting

Other available settings

Output voltage

on battery power

230 Volts AC

200/208/220/240 Volts AC

Overload alarm threshold

105%

30/50/70%

Function

Factory setting

Other available settings

High threshold for transfer to battery

294 Volts AC

271 to 294 Volts AC

Low threshold for transfer to battery

160 Volts AC

160 to 180 Volts AC

Fader activation threshold

265 Volts AC

244 to 265 Volts AC

Booster activation threshold

184 Volts AC

184 to 207 Volts AC

Maximum input-voltage range

Disabled

Enabled

(1)

Function

Factory setting

Other available settings

UPS-sensitivity level

Normal

High or low

Function

Factory setting

Other available settings

Automatic start

Enabled

Disabled

Cold start

Enabled

Disabled

Forced shutdown

Enabled

Disabled

Energy-savings mode

Disabled

Enabled

UPS ON/OFF controlled by software

Enabled

Disabled

Battery level before restart

0%

0 to 100%

Function

Factory setting

Other available settings

Battery-test intervals

Weekly

No test / daily test / monthly test

Low-battery warning

20%

0 to 100%

Battery protection against deep discharge

Enabled

Disabled

Audio alarm

Enabled

Disabled

Additional battery module (Evolution S models only)

Automatic detection of number
of battery modules

For specific batteries, from 25
to 81 Ah