Operating data – Generac Power Systems QT02516 User Manual
Page 3
OPERATING DATA
COMMERCIAL 25 kW
RATING: All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to
varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change
without notice. Maximum wattage and current are subject to and limited by such factors as fuelBtu content, ambient temperature, altitude, engine power and condition, etc.
COMMERCIAL 25 kW
KW RATING
25
ENGINE SIZE
1.6 Liter 4 cyl. inline
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
KW LP
KW NG
AMP LP AMP NG CB Size
120/208V,
3-phase,
0.8
pf
25
24
86.8
83.3
100
120/240V, 3-phase, 0.8 pf
25
24
75.2
72.2
90
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
208 or 240V 3-phase
34
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Natural Gas
Propane
(ft
3
/hr.) (gal/hr.)
cu
ft/hr
Exercise
cycle
60
0.65
24
25% of rated load
161
1.76
64
50% of rated load
253
2.77
101
75% of rated load
345
3.79
138
100% of rated load
437
4.81
175
ENGINE COOLING
Air flow
(inlet air including alternator and combustion air)
ft
3
/min. 1,528
System coolant capacity
US gal.
2.0
Heat rejection to coolant
BTU/hr.
110,000
Max. operating air temp. on radiator
°C (°F)
60 (150)
Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
90
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode
62
db(A) @ 23 feet at normal operating load
74
EXHAUST
Exhaust flow at rated output 60 Hz cfm
249
Exhaust temp. at muffler outlet
°F
1015
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz
3600
HP at rated KW
60 Hz
45
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature
Deration
3% for every 10 °C above - °C
25
1.65% for every 10 °F above - °F
77
Altitude
Deration
1% for every 100 m above - m
183
3% for every 1000 ft. above - ft.
600
COMMERCIAL SERIES