Operating data – Generac Power Systems SD150 User Manual

Page 3

background image

STANDBY

PRIME

SD150

SD150

GENERATOR OUTPUT VOLTAGE/KW-60Hz

Rated AMP

Rated AMP

120/240V, 1-phase, 1.0 pf

150

625

120

500

120/208V, 3-phase, 0.8 pf

150

520

120

416

120/240V, 3-phase, 0.8 pf

150

451

120

361

277/480V, 3-phase, 0.8 pf

150

226

120

180

600V, 3-phase, 0.8 pf

150

180

120

144

GENERATOR OUTPUT VOLTAGE/KVA-50Hz

Rated AMP

Rated AMP

110/220V, 1-phase, 1.0 pf

120

545

96

436

115/200V, 3-phase, 0.8 pf

150

433

120

346

100/200V, 3-phase, 0.8 pf

150

433

120

346

231/400V, 3-phase, 0.8 pf

150

217

120

173

480V, 3-phase, 0.8 pf

150

180

120

144

MOTOR STARTING KVA

Maximum at 35% instantaneous voltage dip

231/240V

400/480V

231/240V

400/480V

with standard alternator; 50/60 Hz

390

405

390

405

with optional alternator; 50/60 Hz

325

338

325

338

FUEL

Fuel consumption—60 Hz

Load

25%

50%

75%

100%

25%

50%

75%

100%

liters/hr.

9.3

17.3

25.1

32.6

7.4

13.8

20.1

26.0

gal./hr.

2.5

4.6

6.6

8.6

2.0

3.6

5.3

6.9

Fuel consumption—50 Hz

liters/hr.

7.4

13.8

20.1

26.0

5.9

11.0

16.0

20.8

gal./hr.

2.0

3.6

5.3

6.9

1.6

2.9

4.2

5.5

COOLING

Coolant capacity

System - lit. (gal)

19.0 (5.0)

19.0 (5.0)

Engine - lit. (gal)

9.8 (2.6)

9.8 (2.6)

Radiator - lit. (gal)

9.2 (2.4)

9.2 (2.4)

Coolant flow/min.

60 Hz - lit. (gal)

159.0 (42.0)

159.0 (42.0)

50 Hz - lit. (gal)

132.5 (35.0)

132.5 (35.0)

Heat rejection to coolant @ full load

BTU/hr.

344,700

275,760

Air to radiator in

60 Hz - m

3

/min. (cfm)

159 (5,600)

159 (5,600)

enclosed unit

50 Hz - m

3

/min. (cfm)

132 (4,667)

132 (4,667)

Max. external pressure drop on radiator

in. H

2

O

0.5

0.5

Max. air temperature to radiator

°C (°F)

48.9 (120)

48.9 (120)

Max. ambient temperature

°C (°F)

43.3 (110)

43.3 (110)

COMBUSTION AIR REQUIREMENTS

Flow at rated power

60 Hz - m

3

/min. (cfm)

14.2 (501.0)

11.3 (400.8)

50 Hz - m

3

/min. (cfm)

11.3 (398.9)

9.0 (319.2)

EXHAUST

Exhaust flow at rated output 60 Hz -

m

3

/min. (cfm)

38.6 (1362)

30.9 (1090)

50 Hz - m

3

/min. (cfm)

30.7 (1085)

24.6 (868)

Max recommended back pressure in. Hg (kPa)

5.1 (1.5)

5.1 (1.5)

Exhaust temperature at rated output

°C (°F)

538 (1000)

538 (1000)

Exhaust outlet size

mm. (in.)

127 (5.0)

127 (5.0)

ENGINE

Rated RPM

60 Hz / 50 Hz

1800 / 1500

1800 / 1500

HP at rated KW

60 Hz / 50 Hz

221 / 176

178 / 141

Piston speed

60 Hz - m./sec. (ft./min.)

7.8 (1535)

7.8 (1535)

50 Hz - m./sec. (ft./min.)

6.5 (1280)

6.5 (1280)

BMEP

60 Hz / 50 Hz - psi

223 / 213

180 / 171

DERATION FACTORS

Temperature

-3.5% for every 10

o

C above - °C

40

40

-2.77% for every 10

o

F above - °F

104

104

Altitude

-1.1% for every 100 m above - m

1066

1066

-3.5% for every 1000 ft. above - ft.

3500

3500

OPERATING DATA

NOTE: Consult your
Generac dealer for
additional voltages.

NOTE: Consult your
Generac dealer for
additional voltage

SD150