Hardware connections – FieldServer NCA2-NFS2-3030 User Manual
Page 4
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 4 of 21
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: [email protected]
3
HARDWARE CONNECTIONS
The FieldServer is connected to the Notifier NCA2/NFS2-3030 Fire Panel as shown in the following connection
drawing.
Configure the Notifier Panel according to manufacturer’s instructions.
FieldServer
FieldServer Part #
8917-16
Pigtail for RJ45
Port
RJ45
Connection to TB5 Printer
Port.
Notifier NCA2/NFS2-3030
Connect to one of the RS-232
Ports on the FieldServer
P1
CTX CRX REF
PTX PRX REF
TB5
Printer
CRT
Rx (Brown)
Tx (Orange/White)
Com (Blue/White)
1
8
Connector Pinouts
TB5 CRT
Function Receive
Reference
Transmit
Pin
CRX
REF
CTX
TB5 Printer
Function Receive
Reference
Transmit
Pin
PRX
REF
PTX
RJ-45
Function Transmit
Com
Receive
Pin
8
4
1
Wire Color
Orange/white Blue/white Brown