UNVENTED PROPANE/LP GAS LOG HEATER

FIREPLACE MANUFACTURERS INCORPORATED

INSTALLATION

Continued

Minimum Noncombustible
Material Clearances

If Not Using Mantel

Note:

If using a mantel, proceed to If Using

Mantel. If not using a mantel, follow the
information below.

You must have noncombustible material(s)
above the fireplace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With
sheet metal, you must have noncombustible
material behind it. Noncombustible material
must extend at least 8" up (for all models). If
noncombustible material is less than 12", you
must install the fireplace hood accessory (24"
and 30" models only). See Figure 5 to the
right for minimum clearances.

IMPORTANT:

If you cannot meet these

minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory for
Vented Operation
, page 10.

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Heat Resistant
Material

(A)

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

12" or more

Noncombustible material OK.

Between 8" and 12"

24", or 30" Models: Install fireplace hood accessory
(GA6050, GA6052, or GA6053, see

Accessories,

page 21).

18" Model: Noncombustible material OK.

Less than 8"

Noncombustible material must be extended to at
least 8". See

Between 8" and 12", above. If you

cannot extend material, you must operate heater
with flue damper open.

NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is
needed. Go to

Installing Damper

Clamp Accessory for Vented
Operation, page 10.

If Using Mantel

You must have noncombustible material(s)
above the fireplace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With
sheet metal, you must have noncombustible
material behind it. Noncombustible mate-
rial must extend at least 8 inches up (for all
models). If noncombustible material is less
than 12", you must install the fireplace hood
accessory (24" and 30" models only). Even

if noncombustible material is more than
12", you may need the hood accessory to
deflect heat away from your mantel shelf.
See Figure 5, and Figures 6 and 7, page 9,
for minimum clearances.

IMPORTANT:

If you cannot meet these

minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory for
Vented Operation
, page 10.