3. run-in procedure using resistance grid – Hobart Welding Products CONTRACTOR 3025 User Manual
Page 46
OM-492 Page 42
9-3.
Run-In Procedure Using Resistance Grid
S-0684
Y
Stop engine.
Y
Do not touch hot exhaust
pipe, engine parts, or load
bank/grid.
Y
Keep exhaust and pipe away
from flammables.
1
Resistance Grid
Use grid sized for generator rated
output.
Turn Off grid.
2
Welding Generator
3
Weld Cables
Connect grid to generator weld
output terminals using proper size
weld cables with correct connec-
tors (polarity is not important).
4
Voltmeter
5
Clamp-On Ammeter
Connect voltmeter and ammeter as
shown, if not provided on generator.
Start engine and run for several
minutes.
Set grid switches and then adjust
generator V/A control so load
equals 225 amps at 30 volts.
Check generator and meters after
first five minutes then every fifteen
minutes to be sure generator is
loaded properly.
.
Check oil level frequently dur-
ing run-in; add oil if needed.
After one hour (minimum), place
V/A control in minimum position,
then shut down grid to remove load.
Run engine several minutes at no
load.
Y
Stop engine and let cool.
6
Engine Exhaust Pipe
Repeat procedure if wetstacking is
present.
1
3
2
5
6
+
4