beautypg.com

Beacon controller, Beacon trouble-shooting guide (cont’d.) – Heatcraft Refrigeration Products BEACON 25001501 User Manual

Page 17

background image

BEACON CONTROLLER

17

BEACON TROUBLE-SHOOTING GUIDE (cont’d.)

System will not run

1. Check if red jumper wire (next to blue pot) is correctly

connected across “X” terminals

2. Check red jumper wire terminals to make sure they are

connected to the wire, not the insulation

3. Check to make sure system is correctly wired
4. Check system for low voltage or high voltage conditions;

system must have voltage between 18-30 VAC for proper
operation

5. Check if “EVAP IN” & “EVAP OUT” sensors are correctly

installed on the board & on copper tubing

6. If system has Smart Controller, check “MULTI IN” & “MULTI

OUT” connection at board & at Smart Controller to make sure
wires are not reversed

7. Check if “ROOM” sensor is connected on Beacon board
8. Check that room sensor is good by resistance check
9. Check refrigerant charge
10. If voltage is too high (above 30 volts) or too low (below

18 volts), unit will not run

Coil frost pattern is uneven

1. Check evaporator coil circuits if they are feeding properly;

uneven feeding will cause uneven icing

2. If liquid line runs through cooled space, may need to be

insulated or nozzle reselected for conditions

3. If electric defrost coil for medium temperature applications,

medium temperature nozzle must be installed