Specifications
Ordering Information
Small Enclosure
Large Enclosure
I/O Expansion Module
UMS02400
115VAC
UML11500
230VAC
UML23000
UMEXP
Input Power
Requirements
24VAC±10% of
nominal; 50/60 Hz,
1.3A, 30VA
115VAC±10% of
nominal; 60Hz,
4A, 460VA
230VAC±10% of
nominal; 50Hz,
0.5A, 115VA
24VAC±10% of
nominal; 50/60 Hz,
0.6A, 15VA, Class 2
Dimensions
W x D x H, in. (mm)
14-1/4 x 2-3/4 x 12
(361.95 x 69.85 x 304.8)
18 x 2-3/4 x 18
(457.2 x 69.85 x 457.2)
14-1/4 x 2-3/4 x 12
(361.95 x 69.85 x 304.8)
Weight (Assembled)
7.68 lb. (3.48 kg)
20.56 lb. (9.33 kg)
7.68 lb. (3.48 kg)
Enclosure Type
NEMA 1
NEMA 1
Liquid Crystal Display
Four line, 20 character, backlit
—
Mounting Surface
Building Wall or Structural Member
Ambient Operating
Environment
32°F to 104°F (0°C to 40°C)
0% RH to 95% RH (non-condensing)
Modem/Clock Specifics
—
Modem Type
Embedded 14.4K bps
—
Clock Type
Real-Time Clock
—
Clock battery backup type
Lithium Cell (non-replaceable)
—
Clock battery life
7 years, constant, no power
—
Modem battery backup type
Nickel Cadmium (replaceable)
—
Modem battery life
10 minutes at full load
—
Communications
—
Local
EIA232
—
Remote: Modem
Baud rate 9600 bps; Parity=None; Data bits=8; Stop bits=1
—
Remote: Supported pagers
9600 E-7-1 supports TAPI protocol version 1.8
—
SiteScan Web
IGM Protocol, EIA422
—
Expansion Board (optional)
EIA485
EIA485
Agency Listings
UL
UL3121
UL1012
UL1585
—
CSA
C22.2 No. 1010
C22.2 No. 66 and C22.2 No. 107.1
—
CE
Yes
Yes
—
FCC Compliance
CFR 47 Part 15
N/A
—
Inputs & Outputs (Quantity)
Digital Inputs
Dry Contact Closure
24VDC, 10 mA (8)
Dry Contact Closure
24VDC, 10 mA (16)
Analog Inputs
4-20mA signal input with selectable power source of 12VDC or 24VDC (4)
—
Digital Outputs
24VAC, 3A (8)
240VAC, 2A (8)
Common Alarm Outputs
24VAC, 3A (2)
—
Quantity
Product #
Description
UMS02400
Universal Monitor small enclosure
UML11500
Universal Monitor large enclosure with 115VAC Transformer Module
UML23000
Universal Monitor large enclosure with 230VAC Transformer Module
TM115
Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC receptacle
TM230
Transformer Module 230VAC with two 24VAC outputs (40VA each)
UMEXP
I/O Expansion Module