beautypg.com

Ch 4 - discrete input modules, Pointscan/221, Overview – Measurement Computing PointScan 200 Series rev.1.0 User Manual

Page 19: Standard wiring, Optional wiring, I/o registers, 4 - discrete input modules, 8 discrete inputs / counters, With direct field wiring base, With isolated inputs

background image

PointScan/200 User’s Manual

9-12-01

Discrete Output Modules 4-1

Discrete Input Modules

4

PointScan/221

8 Discrete Inputs / Counters with Direct Field Wiring Base

PointScan/221

8 Discrete Inputs / Counters with Isolated Inputs

Overview

The standard field wired base provides a pre-wired connection to DC power for each of the eight discrete
input channels. For applications which require individually isolated, ground sinking,
or AC inputs, the optional universal wiring base is recommended. An input count feature uses analog input
registers to accumulate the positive transitions of each input. More information on this and other features
can be found in the on-line help supplied with the IO Toolkit.

Number of Channels

8 discrete inputs with pulse counter feature

Input Voltage Range

10 - 30 VDC (standard), 10 - 30 VDC/VAC (optional)

Maximum Count Rate

100 Hz (6000 / minute) each input, plus selectable 2KHz (120,000 / minute)
mode for input 1 only

Standard Wiring

The even numbered terminals (2 - 16) on this field wiring ready base are pre-wired to the DC power (+)
terminal. Adjacent pairs of terminals are connected to each input (switch) device.

Optional Wiring

A pair of floating terminals is provided for each input to provide channel-to-channel isolation
(floating inputs) and a choice of sourcing (power switching), sinking (ground switching) or AC signals on
each input.

I/O Registers

Function

IOtech Registers

Modbus Registers

Discrete Inputs

X0 - X7

10001 – 10008

Counter Inputs

AX0 - AX7

30001 - 30008 Unsigned values: 0

Æ 65,535