Operation, How to diagnose assembly/model faults – GAI-Tronics 12578-003 Monitored Input Module (MIM) User Manual
Page 10

Pub. 42004-715L2C
Model 12578-003 Monitored Input Module (MIM)
Page 10 of 12
f:\standard ioms - current release\42004 instr. manuals\42004-715l2c.doc
06/12
Operation
The operation of the Model 12578-003 MIM is controlled by the MCU configuration. See the MCU
configuration details in the system manual for all operation information.
How to Diagnose Assembly/Model Faults
Symptom Action
MIM does not
communicate
with MCU
Verify power is applied to the MIM.
Verify page line is connected to the MIM.
Verify address of MIM agrees with the setup configuration.
Ensure CPU PCBA is correctly connected via J1.
Call for service of the MIM.
MIM does not
recognize dry
inputs
Verify total loop resistance is less than 100 .
Verify power is applied to the MIM.
Verify page line is connected to the MIM.
Verify end of line resistor(s) properly installed on each input circuit.
Call for service of the MIM.
MIM does not
activate an
alarm with 24 V
dc applied to
input terminal.
(Wet contact
mode ONLY.)
Verify that the jumper that selects the proper “_ V dc when active” mode is in
the correct position for the desired mode. Refer to Mode 5 - IDC Non-
Supervision (Wet Contact) information.
Verify that the applicable input jumpers have been repositioned for WET
operation.
Verify that the input is within the acceptable dc voltage range (20–30 V dc)
Verify that the proper voltage polarity has been observed for external
connections to the input terminals.
Call for service of the MIM.