Common 24 vac output – Viconics C1024 User Manual
Page 2

Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9
www.viconics.com
LIT-C1024-E01
A) Location:
1- Shouldn’t be installed on outside wall.
2- Must be installed away from any heat source.
3- Shouldn’t be affected by direct sun radiation.
4- Nothing must restrain vertical air circulation to the
thermostat.
B) Installation:
1- Pull out cables 6” out of the wall.
2- Wall surface must be flat and clean.
3- Separate the thermostat and the base by pulling the
cover by the bottom (same as the security screw.)
4- Insert cable in the central hole of the base.
5- Align the base and mark the location of the two
mounting holes on the wall. Install proper side of
base up.
6- Install shields in the wall.
7- Insert screws in mounting holes on each side of the
base. DO NOT OVERTIGHTEN!
8- Strip each wire 1/4 inch.
9- Insert each wire according to wiring diagram.
10- Reinstall the cover ( top side first ) and gently push
back extra wire length in the hole in the wall.
11- Install security screw.
DIP switch ADJUSTMENT per applications
S1
APPLICATION SWITCH
0
Heating with N.C. valves
Cooling with N.O. valves
1
Heating with N.O. valves
Cooling with N.C. valves
CONTROL CURVE AND SEQUENCE
TYPICAL APPLICATIONS
Room Temperature Control With:
Thermoelectric Valve Actuators
Dip switch position
S1
Heating with N.C. valves
Cooling with N.O. valves
0
Heating with N.O. valves
Cooling with N.C. valves
1
The output is rated at 0.5 A. max at 30 Vac.
50 %
100%
0%
Temperature increase
Power ON
DIAL SETPOINT
S1 = 0
Cooling N.O.
&
Heating N.C.
Power OFF
S1 = 1
Cooling N.C.
&
Heating N.O.
Common
24 Vac
Output
3
4
5
N.C. Valve Heating
&
N.O. Valve Cooling
Room Temperature
Control Thermostat
50
70
60
90
80
F
N.O. Valve Heating
&
N.C. Valve Cooling
Room Temperature
Control Thermostat
50
70
60
90
80
F