beautypg.com

SilentKnight SKE-ZN4 Zone Splitter User Manual

Ske-zn4 zone splitter installation instructions, Compatibility, Mounting

background image

P/N 151394

SKE-ZN4 Zone Splitter Installation

Instructions

The SKE-ZN4 is an evacuation zone splitter for
use with the SKE-450. The SKE-ZN4 is capable
of splitting the audio output from the main amp
into four separate audio output zones or
channels.
The SKE-ZN4 can be used in installations where
the audio must be split to different floors or
zones to accommodate a safe and efficient
evacuation process.

Note: Installation and wiring of this device must be done in

accordance with NFPA 72 and local ordinances.

Compatibility

The SKE-ZN4 is compatible with the SKE-450
control panel.

Mounting

1. Unlock and open the SKE-450 control panel

cabinet door.

2. Open the control panel cover door by

removing the two retaining screws and
rotating the door to the left. See Figure 1.

Figure 1: SKE-450 Cabinet With Control Panel Cover In

Place

3. Remove the SKE-ZN4 access plate.
4. Mount the SKE-ZN4 to the SKE-450 cabinet

mounting standoffs with the 7/10” screw-in
standoffs provided.

Figure 2: SKE-ZN4 Mounting Standoff Locations

5. Connect wiring harness to the expansion

connector on the SKE-450 and to the direct
connect pins on the SKE-ZN4. See Figure 3.

Note: Speaker outputs of the SKE-450 must not be used with the

SKE-ZN4 because supervision will not be provided at the
SKE-450.

Figure 3: View With SKE-ZN4 Installed

6. Wire speaker to zone outputs as required by

the installation specifications. See the
Speaker Wiring
section.

7. Attach the cover plate to the SKE-ZN4. See

Figure 3.

Control Panel

Cover Retaining

Screws

Control Panel

Cover Door

SKE-ZN4 Access
Plate

SKE-ZN4
Mounting
Standoffs

15 k

Ω EOL

UL Listed

Model 7630

SKE-

ZN4

Cover

Wiring Harness

(PN 130398)