beautypg.com

Messages and emergency operation – GEA Bock BCM2000 User Manual

Page 13

background image

13

D
GB
F
E

09794

-05.2012-DGbFEI

Messages and emergency operation

Oil pressure too low
LED ON / Compressor OFF

Switch 4 Off

Reset

Reset

4

Fault message

Compressor starts up immedi-

ately.

LED OFF

Compressor starts up through

machine control. LED flashes

Fault message

Combined function 2:
Compressor not turning.
LED ON / Compressor OFF

5 + 6 are bridged. Compressor

starts up through machine control.

LED flashes

Switch 5 Off

Reset

Reset

5

6

Only 6 is bridged. Compressor

starts up through machine control.

LED OFF

Switch 6 Off

Reset

Surge op. too high
LED ON / Compressor ON

Switch 7 Off

Reset

Reset

Information message

7

LED OFF

Reset to „0“

Counting starts again

12 starts per hour

exceeded

Recommended oil change
LED ON / Compressor ON

Switch 8 Off

Reset

Reset

Information message

8

LED OFF

Reset to „0“

Evaluation starts again

Combined function 1:
Liquid at start
LED ON / Compressor OFF

Display

a) Reset to initial function

b)

Function bridged (emergency

operation - no safety function)

Compressor starts up

immediately.

LED OFF

Compressor starts up through

machine control. LED flashes

Compressor starts up through

machine control. LED flashes

Reset

Compressor starts up

after fault eliminated.

LED OFF

Fault message

Engine monitoring by win-
ding temperature feeler

+

+

+

+

+