beautypg.com

tekmar 352 House Control User Manual

Page 5

background image

Copyright © D 352 - 06/00

5 of 8

• Run the wires from the 24 V (ac) power source or heat demand to the control mounting location.

Use a clean power source to ensure

proper operation.

• If a tekmar Timer 031 is used, follow the installation procedure provided in the Data Brochure D 031 and run the wiring back to the

control mounting location.

STEP FOUR

TESTING THE WIRING

No wires should be connected to the control during testing.

A good quality electrical test meter, capable of reading from at least 0 — 200 V (ac) and at least 0 — 2,000,000 Ohms, is essential to
properly test the wiring and sensors.

Test the Sensors

Test the sensors and RTU according to the testing procedure in Data Brochures D 070
and D 054.

Test the Power Supply

Make sure exposed wires and bare terminals are not in contact with other wires or
grounded surfaces. Turn on the power and measure the voltage across the 24 V (ac)
power supply. The voltmeter should read between 22 and 26 Volts.

Test the Outputs

• Short the system pump wires and power up the pump circuit; the system pump should turn on. Remove the power from the system

pump circuit.

• If the control is in

Boiler mode, short the boiler wires and power up the boiler circuit; the boiler should fire. Remove the power from

the boiler circuit.

• If the control is in

Injection mode, short the valve wires and power up the valve circuit; the valve should open. Remove the power

from the valve circuit and the valve should close.

STEP FIVE

ELECTRICAL CONNECTIONS TO THE CONTROL

The installer should confirm that no voltage is present at any of the wires.

Output Connections

System Pump

Connect one of the wires from the system pump to one of the wires from the back of
the control. Connect the second wire from the back to the live (L) side of the 120 V (ac)
power source. The other wire on the system pump must be connected to the neutral
(N) side of the 120 V (ac) power supply. Refer to application brochures A 352.

Insert the low voltage wiring into the wiring chambers on the control and mount the 352
on the electrical box.

Heat Relay

If the DIP switch is set to

Boiler, connect the 120 V (ac) or 24 V (ac) boiler circuit directly

to the

Heat relay (3 and 4) terminals.

If an injection valve or pump is used, connect one of the wires from the valve or pump
to the

Heat relay (4) terminal and the other wire to the common or neutral side (C for

24 V (ac) or N for 120 V (ac)) of the power supply. Connect the

Heat Relay (3) terminal

to the live (R for 24 V (ac) or L for 120 V (ac)) side of the power supply.

Powered Input Connections

24 V (ac) Power

Connect the 24 V (ac) power supply to terminals

Power C— R (1 and 2) on the control.

Sensor and Unpowered Input Connections

Do not apply power to these terminals as this will damage the control.

Outdoor Sensor

Connect the two wires from the Outdoor Sensor 070 to the terminals

Com Sen — Out

Sen (7 and 9). The Outdoor Sensor measures the outdoor air temperature.

Supply Sensor

Connect the two wires from the Supply Sensor 071 to the terminals

Com Sen — Sup

Sen (7 and 8). The Supply Sensor measures the supply water temperature to the
system.

RTU

Sen

6

8

Sup

Sen

UnO

Sw

5

Com

Sen

7

Out

Sen

9

RTU

Sen

6

8

Sup

Sen

UnO

Sw

5

Com

Sen

7

Out

Sen

9

3 4

1 2

Power

Relay

Heat Heat

R

C

3 4

1 2

Power

Relay

Heat Heat

R

C

STOP

Refer se

rvicing to

qualified

personn

el. Open

ing voids

warranty

.

Pump
(black)

Live power
(black)