6C. LOOP RESISTANCE VS. POWER SUPPLY

______________________________________________________________________________________________________________

6D. RECOMMENDED SAFETY BARRIERS FOR INTRINSICALLY
SAFE INSTALLATIONS

____________________________________________________________________________________________________________

NOTES:
1.

When selecting barrier types, the electrical specifications for the transmitter are:
• Vmax = 36.1 Vdc
• Imax = 118 mA
• Ci = 0.0 µF
• Li = 0.0 µHy

2.

KENCO recommends the following safety barrier:
• Stahl Model Number 9001/01-280-100-10