Rockwell Automation Flex/WebPak 3000 DC Drive Inverting Fault CB Kit 1.5-30HP-230VAC, 3-60HP-460VAC User Manual
Product description
©2001 Rockwell International Corporation
FlexPak, WebPak, and Reliance are trademarks of Rockwell Automation
Inverting Fault Circuit Breaker Kit
for FlexPak 3000 and WebPak 3000 Digital DC Drives
1.5 - 30 HP @ 230 VAC and 3-60 HP @ 460 VAC
Model Numbers: 906FK0101, 906FK0201, 906FK0301, 906FK0401, and 906FK0501
Instruction Manual D2-3300-2
Product Description
This instruction manual describes how to install the optional Inverting Fault Circuit Breaker kit on regenerative
FlexPak
3000 and WebPak
3000 drives (1.5-30 HP @ 230 VAC and 3-60 HP @ 460 VAC.) Use of this kit is
recommended when applying regenerative drives to high inertia loads. High inertia loads are those in which
the reflected load to the motor is equal to or greater than the motor’s load, or in which the drive is frequently
regenerating power to the AC line, such as in unwind and pay-off application.
An inverting fault typically occurs as a result of a loss of the AC line. If this happens, the AC input transformer
becomes a short circuit across the motor. Since the SCRs in the bridge no longer turn off, the motor’s stored
mechanical energy is regenerated into the short circuit. The inverting fault circuit breaker interrupts the
generator action, protecting the SCR bridge and the motor.
In addition to the parts included in the kit, you must supply an appropriate mounting panel for the inverting fault
circuit breaker and provide circuit breaker wiring.
Important: If any other interlocks are required for your application, they must be connected in series to the
Customer Interlock Input along with the circuit breaker.
!
ATTENTION: Only qualified personnel familiar with the construction and operation of this
equipment and the hazards involved should install, adjust, operate, and/or service this equipment.
Read and understand this instruction manual in its entirety before proceeding. Failure to observe
this precaution could result in severe bodily injury or loss of life.
ATTENTION: The user is responsible for conforming with all applicable local, national, and
international codes. Failure to observe this precaution could result in damage to, or destruction
of, the equipment.
Table 1 – Verifying That the Inverting Fault Circuit Breaker Matches the Drive
Drive Horsepower/Voltage Rating
Kit Model Number
1.5 - 2 HP @ 230 VAC
3 - 5 HP @ 460 VAC
906FK0101
3 - 5 HP @ 230 VAC
7.5 - 10 HP @ 460 VAC
906FK0201
7.5 - 10 HP @ 230 VAC
15 - 20 HP @ 460 VAC
906FK0301
15 - 20 HP @ 230 VAC
25 - 40 HP @ 460 VAC
906FK0401
25 - 30 HP @ 230 VAC
50 - 60 HP @ 460 VAC
906FK0501