Compact™ 1769-IF4 (Series B or Later) Analog Input Module 15
Publication 1769-IN048A-EN-P
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
Input Data File
For each input module, slot x, words 0-3 in the input data file contain the
analog values of the inputs.
The bits are defined as follows:
• SGN = Sign bit in two’s complement format
• Sx = General status bit for channels 0 through 3. This bit is set (1) when
an error (over- or under-range) exists for that channel.
• Ux = Under-range flag bits for channels 0 through 3. These bits can be
used in the control program for error detection.
• Ox = Over-range flag bits for channels 0 through 3. These bits can be
used in the control program for error detection.
Wire Type
Wire Size
Terminal Screw
Torque
Retaining Screw
Torque
Solid
Cu-90°C (194°F)
#14 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Stranded
Cu-90°C (194°F)
#16 to #22 AWG
0.68 Nm (6 in-lbs)
0.46 Nm (4.1 in-lbs)
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
SGN
Analog Input Data Channel 0
1
SGN
Analog Input Data Channel 1
2
SGN
Analog Input Data Channel 2
3
SGN
Analog Input Data Channel 3
4
Not Used
S3
S2
S1
S0
5
U0
O0
U1
01
U2
O2
U3
O3
Set to 0