Model 505.60 HPU Setup
Operation
Model 505.60 HPU Setup
Pressure Filter
display
Indicates yellow when the filter needs replacement. The signal can be
monitored from the system controller.
Refer to the appropriate filter replacement procedure if necessary.
After replacing the filter, press the Reset button to clear the indication. The
indicator returns to Pressure Filter Normal (green).
Pump Motor Overload
Fault Status display
Monitors each enabled pump motor and indicates red when a thermal overload
has been detected.
Pump Motor Run Status
display
Indicates the current run status of each pump. The possible conditions are:
•
Enabled
•
Offline
•
On-Low
•
On-High
•
Standby (After the first pump starts, this term displays on all
remaining enabled pumps until they start.)
HPU Status Screen (Continued)
Control
Descriptions