Wiring the device modules
Safety modules
l
82
EDK94ASH24 DE/EN/FR/ES/IT 4.1
X82.4
Labelling
Description
GCL
GND clock output
GI4
GND SD−In4
I4B
Sensor input SD−In4, channel B
I4A
Sensor input SD−In4, channel A
GCL
GND clock output
GI3
GND SD−In3
I3B
Sensor input SD−In3, channel B
I3A
Sensor input SD−In3, channel A
AIS
Restart acknowledgement input ("Acknowledge In Stop", 1−channel,
bridged to X82.3/AIS)
Cable cross−sections and tightening torques
Type
[mm
2
]
[Nm]
AWG
[lb−in]
Wire end ferrule,
insulated
0.25 ... 0.75
Spring terminal
24 ... 18
Spring terminal
Rigid
0.14 ... 1.5
26 ... 16
Stripping length or contact length: 9 mm
Displays
Pos.
Colour
State
Description
MS
(Module State)
Green
On
Drive−based safety is initialised faultlessly.
Blinking
Drive−based safety is initialised faultlessly. Internal
communication to the basic device is not possible.
Flashing
Drive−based safety is in service status.
For exiting, parameterise the drive−based safety.
Off
Drive−based safety is not initialised.
Acknowledgement is not possible.
EN
(Enable)
Yellow
On
Controller enabled
Off
Non−safe display "STO"
ME
(Module Error)
Red
On
System error
Blinking
Trouble
Flashing
Warning
Off
Error−free operation
AS
(Acknowledge Stop)
Yellow
On
Request of an acknowledgement for the restart or the
parameter set adoption
Blinking
SS1/STO active
Flashing
SS2/SOS active
Off
No stop function active
BE
(Bus Error)
Red
On
Safety bus error:
l
Communication is not possible.
l
Acknowledgement is possible.
Blinking
Safety bus error: no valid configuration.
Off
Safety bus: error−free operation.
DE
(Drive Error)
Red
On
Drive−based safety is not accepted by the basic device (see
notes in the instructions for the basic device).
Off
Drive−based safety is correctly recognised by the basic device.
Blinking: on/off every 0.5 s Flashing: on/off every 0.1/0.9 s