beautypg.com

Ventilation air from outdoors, Warning – New Buck Corporation 1110 User Manual

Page 18

background image

Figure 9

VENTILATED ATTIC

OUTLET AIR

OUTLET AIR

INLET AIR

TO ATTIC

TO
CRAWL
SPACE

INLET AIR

VENTILATED
CRAWL SPACE

VENTILATION AIR FROM OUTDOORS


Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent
openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items
directly to the outdoors. These spaces include attics and crawl spaces. Follow the National
Fuel Gas Code NFPA 54/ANSI Z223.1
, Section 5.3, “Air For Combustion and Ventilation”
for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic will activate the power unit.

WARNING

THIS APPLIANCE MUST HAVE FRESH AIR FOR PROPER OPERATION. IF NOT,
POOR FUEL COMBUSTION COULD RESULT. READ THE FOLLOWING
INSTRUCTIONS TO ENSURE PROPER FRESH AIR FOR THIS AND OTHER FUEL-
BURNING APPLIANCES IN YOUR HOME.

16